SiAU18-715
Field Setting
Test Operation
149
3.2.3
Setting of Refrigerant Additional Charging Operation
Service port
for additionally
charging the refrigerant
When the outdoor unit is stopped and the entire quantity of refrigerant cannot be charged from the stop valve on the liquid sid
e, make sure
to charge the remaining quantity of refrigerant using this procedure. If the refrigerant quantity is insufficient, the unit may malfunction.
Turn ON the power of the indoor unit and the outdoor unit.
Make sure to completely open the stop valve on the gas side and the stop valve on the liquid side.
Connect the refrigerant charge hose to the service port (for additionally charging the refrigerant).
In the stopped status, set to ON the refrigerant additional charging operation A in
The operation is automatically started.
(The LED indicator H2P flickers, and “Test run” and “Under centralized control” are displayed in the remote controller.)
After charging the specified quantity of refrigerant, press the RETURN button (BS3) to stop the operation.
The operation is automatically stopped within 30 minutes.
If charging is not completed within 30 minutes, set and perform the refrigerant additional charging
operation A again.
If the refrigerant additional charging operation is stopped soon, the refrigerant may be overcharged.
Never charge extra refrigerant.
Disconnect the refrigerant charge hose.
Refrigerant additional charging operation procedure
set mode 2 (H1P: Turn on).
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...