SiAU18-715
BP Unit Control
Function
97
6.2
BP Unit Electronic Expansion Valve Control
Purpose of the
Function
This function provides instructions regarding the absolute flow rate, relative flow rate and fully
closing from the outdoor unit to the BP unit in order to ensure outdoor unit compressor safety
and optimum refrigerating cycle of the system.
With the transmission a permit/prohibit flag for each distribution control in the BP unit, the
distribution control startup timing is controlled by the outdoor unit.
6.2.1 Electronic Expansion Valve Initial Opening Setting
Outline
This function improves stability of the system to set initial opening of electronic expansion valve
at starting operation.
When the EV opening command from outdoor unit is lifted, the following opening setting is
performed.
During Cooling
Operation
Target EV opening = 2.5 × (DA - 14) + P5 - KEVOPC × (DOA - DA) pls
DA: room temperature, DOA: outdoor air temperature
During Heating
Operation
Target EV opening = 350 pls
6.2.2 Electronic Expansion Valve Flow Rate Restriction
This function prevents the deviation from the electronic expansion valve specification range by
restricting the electronic expansion valve flow rates of the operating and non-operating room
units during compressor operation. It also prevents the generation of abnormal noise such as
refrigerant flowing sound by restricting the circulation of refrigerant according to the operating
conditions (unit ON/OFF) of room units.
Outline
Restriction of electronic expansion valve opening degrees of operating room units;
... Restriction of maximum and minimum flow rates based on constant
Restriction of electronic expansion valve opening degrees of non-heating room units;
... Restriction of minimum flow rate based on constant
... Maximum flow rate determined based on flow rates of operating room units
P5:
KEVOPC:
Indoor unit capacity
P5
KEVOPC
2.0 to 3.5 kW class
140
DOA
≤
DA
0
5.0 kW class
156
DA
<
DOA
2.5
6.0, 7.1 kW class
170
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...