SiAU18-715
Other Control
Function
95
5. Other Control
5.1
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adaptor is required.
[Demand 1 setting]
5.2
Heating Operation Prohibition
Heating operation is prohibited above 24°CDB outdoor air temperature.
Setting
Standard for upper limit of power consumption
Demand 1 setting 1
Approx. 60%
Demand 1 setting 2 (factory setting)
Approx. 70%
Demand 1 setting 3
Approx. 80%