background image

6

NOTES:

1) OUTDOOR THERMOSTAT (OT-1) SHOULD BE THE

     FIRST TO CLOSE AND THE LAST TO OPEN.
2) CONNECT WHITE AND BROWN WIRES FROM AIR-
     HANDLER TOGETHER IF OT-2 IS NOT USED.
3) REMOVE WIRE WHEN USING OUTDOOR THERMOSTAT
4) TERMINAL BLOCK MARKINGS ARE FOR AMANA® BRAND
    AIRHANDLERS.

NOMENCLATURE
OT ---OUTDOOR  THERMOSTAT (OPTIONAL)
EHR -EMERGENCY HEAT RELAY (O PTIONAL)

COLOR CODES
R --RED
Y --YELLOW
BL-BLUE
BR-BROWN
O --ORANGE
W -WHITE
G --GREEN

W2

TYPICAL H/P

ROOM THERMOSTAT

HEAT PUMP

SYSTEM COMPOSITE DIAGRAM

HEAT PUMPS

10 KW & BELOW

(O PTIONAL)

OU TDOO R THERM OSTAT

CLOSE O N  TEM PERATURE  FALL

R

G

C

W2

RED

GREEN

WHITE

BLUE

INDOOR UNIT

R

Y

O

W

BL

#18 GA. 5 WIRE

#18 GA. 7 WIRE

SEE 

NOTE

R

G

BR

W

BL

SEE NOTE #4

R
E
D

Y
E
L
L
O

W

O
R
A
N
G
E

W

H

I

T
E

B
L
U
E

#18  GA. 6  W IRE NEED ED  W HEN OT IS U SED

BL

W

G

R

C

O

Y

R

Y

O

C

W2

G

R

E

O
R
A
N
G
E

Y
E
L
L
O

W

#18  GA . 7 WIRE NEED ED  W H EN  TWO  OT'S A RE USED

#18 GA. 5 WIRE

BL

O

W

Y

SEE NOTE #4

BL

SEE 

NOTE

W

G

C

BLUE

W2

G

WHITE

GREEN

TYPICAL H/P

ROOM THERMOSTAT

SYSTEM COMPOSITE DIAGRAM

HEAT PUMPS

ABOVE 10 KW

HEAT PUMP

B
L
U
E

W

H

I

T
E

R
E
D

R

#18 GA. 7 WIRE

R

INDOOR UNIT

R

RED

W3

BROWN

SEE 
NOTE

(O PT ION AL)

OU TD OOR THERM O STAT

CLOSE O N TEMPERATU RE  FALL

BR

R

G

BR

BL

W2

C

O

Y

R

Y

O

C

W2

G

R

E

 Thermostat

with Low Voltage Wires to Heat Pump Unit

System Start Up

NOTE: Units with crankcase heaters should have high voltage
power energized for 24 hours prior to start up.

Heat pumps are equipped with a time/temperature defrost
control with field selectable defrost intervals of 30, 60, or 90
minutes.  This setting should be adjusted at this time if needed.
The defrost control also has SmartShift™ technology, which
delays compressor operation at defrost initiation and
termination.  If disabling this function is desired, move the
jumper from “DLY” to “NORM” on the defrost control

Adequate refrigerant charge for the matching HSVTC evaporator
coil and 15 feet of lineset is supplied with the condensing unit. If
using evaporator coils other than HSVTC coil, it may be necessary
to add or remove refrigerant to attain proper charge. If line set
exceeds 15 feet in length, refrigerant should be added at .6 ounces
per foot of liquid line.
NOTE: Charge should always be checked using superheat when
using a piston and subcooling when using TXV equipped indoor
coil to verify proper charge.

Open the suction service valve first! If the liquid service valve is
opened first, oil from the compressor may be drawn into the in-
door coil TXV, restricting refrigerant flow and affecting operation
of the system.

POSSIBLE REFRIGERANT LEAK
To avoid a possible refrigerant leak, open the service valves until
the top of the stem is 1/8” from the retainer.

CAUTION

When opening valves with retainers, open each valve only until
the top of the stem is 1/8” from the retainer.  To avoid loss of
refrigerant, DO NOT apply pressure to the retainer. When opening
valves without a retainer remove service valve cap and insert a
hex wrench into the valve stem and back out the stem by turning
the hex wrench counterclockwise. Open the valve until it contacts
the rolled lip of the valve body.

NOTE:  These are not back-seating valves. It is not necessary to
force the stem tightly against the rolled lip.

After the refrigerant charge has bled into the system, open the
liquid service valve. The service valve cap is the secondary seal
for the valve and must be properly tightened to prevent leaks.
Make sure cap is clean and apply refrigerant oil to threads and
sealing surface on inside of cap. Tighten cap finger-tight and then
tighten additional 1/6 of a turn (1 wrench flat), or to the following
specification,  to properly seat the sealing surfaces.

1. 3/8” valve to 5 - 10 in-lbs

2. 5/8” valve to 5 - 20 in-lbs

3. 3/4” valve to 5 - 20 in-lbs

4. 7/8” valve to 5 - 20 in-lbs

Do not introduce liquid refrigerant from the cylinder into the
crankcase of the compressor as this may damage the compressor.

1. Break vacuum by fully opening liquid and suction base

valves.

2. Set thermostat to call for cooling.  Check indoor and outdoor

fan operation and allow system to stabilize for 10 minutes
for fixed orifices and 20 minutes for expansion valves.

Summary of Contents for DZ13SC

Page 1: ...e is delivered at the specified airflow See outdoor unit specification sheet for split system models or product specifica tion sheet for packaged and light commercial models Specifica tion sheets can be found at www daikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be insta...

Page 2: ...on in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pump unit bases have cutouts under the outdoor coil that permit drainage of frost accumulation Situatetheunittopermitfreeunobstructeddrainage of the defrost water and ice In more severe weather locations it is recommended that the unit be elevated to allow unobstructed drainage and air flow ...

Page 3: ... or TP 107 Long Line Set Application R 410A or contact your dis tributor for assistance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4 3 8 2 1 2 5 8 1 4 3 4 3 8 7 8 3 8 3 3 4 3 8 7 8 3 8 1 1 8 3 8 3 1 2 7 8 3 8 1 1 8 3 8 1 1 8 3 8 4 7 8 3 8 1 1 8 3 8 1 1 8 3 8 5 7 8 3 8 1 1 8 3 8 1 1 8 3 8 Line Diameter In OD RECOMMENDED INTERCONNECTING TUBING Ft 0 24...

Page 4: ...ially important on suction line filter driers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart pa...

Page 5: ...allation instructions supplied with the indoor furnace air handler for spe cific wiring connections and indoor unit configuration Likewise consult the instructions packaged with the thermostat for mount ing and location information Overcurrent Protection The following overcurrent protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time ...

Page 6: ...il it may be necessary to add or remove refrigerant to attain proper charge If line set exceeds 15 feet in length refrigerant should be added at 6 ounces per foot of liquid line NOTE Charge should always be checked using superheat when using a piston and subcooling when using TXV equipped indoor coil to verify proper charge Open the suction service valve first If the liquid service valve is opened...

Page 7: ...res to stabilize then check subcooling and or superheat as detailed in the following sec tions Superheat Suct Line Temp Sat Suct Temp Subcooling Sat Liquid Temp Liquid Line Temp To prevent personal injury carefully connect and disconnect manifold gauge hoses Escaping liquid refrigerant can cause burns Do not vent refrigerant into the atmosphere Recover all refrigerant during system repair and befo...

Page 8: ... n a 123 445 n a 125 475 n a 130 500 n a 134 525 n a 138 550 n a 142 575 n a 145 600 n a 149 625 n a 152 SATURATED LIQUID PRESSURE TEMPERATURE CHART SATURATED LIQUID TEMPERATURE ºF SUCTION PRESSURE PSIG R 22 R 410A 50 26 1 52 28 3 54 29 4 56 31 6 58 32 7 60 34 8 62 35 10 64 37 11 66 38 13 68 40 14 70 41 15 72 42 16 74 44 17 76 45 19 78 46 20 80 48 21 85 50 24 90 53 26 95 56 29 100 59 31 110 64 36 ...

Page 9: ... 7 to 9 ºF and superheat of 7 to 9 ºF a If subcooling and superheat are low adjust TXV to 7 to 9 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 7 to 9 ºF then check superheat c If subcooling and superheat are high adjust TXV valve ...

Page 10: ...ltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Remove Restriction Replace Restricted Part Open Element or Limit on Elec Heater Test Heater Element and Controls Dirty Air Filter Inspect ...

Page 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 12: ...ep the outdoor coil clean Dirt leaves or debris could also restrict the airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refriger ant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a conde...

Reviews: