background image

4

Refrigerant Line Connections

IMPORTANT

To avoid overheating the service valve, TXV valve, or filter
drier while brazing, wrap the component with a wet rag, or
use a thermal heat trap compound. Be sure to follow the
manufacturer’s instruction when using the heat trap
compound. Note: Remove Schrader valves from service valves
before brazing tubes to the valves. Use a brazing alloy of 2%
minimum silver content. Do not use flux.

Torch heat required to braze tubes of various sizes is
proportional to the size of the tube. Tubes of smaller size
require less heat to bring the tube to brazing temperature
before adding brazing alloy. Applying too much heat to any
tube can melt the tube. Service personnel must use the
appropriate heat level for the size of the tube being brazed.
Note: The use of a heat shield when brazing is recommended
to avoid burning the serial plate or the finish on the unit.

1. The ends of the refrigerant lines must be cut square, de-

burred, cleaned, and be round and free from nicks or dents.
Any other condition increases the chance of a refrigerant
leak.

2.  “Sweep” the refrigerant line with nitrogen or inert gas dur-

ing brazing to prevent the formation of copper-oxide inside
the refrigerant lines.  The POE oils used in R-410A applica-
tions will clean any copper-oxide present from the inside of
the refrigerant lines and spread it throughout the system.
This may cause a blockage or failure of the metering device.

3. After brazing, quench the joints with water or a wet cloth to

prevent overheating of the service valve.

4. Ensure the filter drier paint finish is intact after brazing.  If

the paint of the steel filter drier has been burned or chipped,
repaint or treat with a rust preventative.  This is especially
important on suction line filter driers which are continually
wet when the unit is operating.

NOTE:  Be careful not to kink or dent refrigerant lines.  Kinked or
dented lines will cause poor performance or compressor damage.

Do NOT make final refrigerant line connection until plugs are
removed from refrigerant tubing.

NOTE:  Before brazing, verify indoor piston size by checking the
piston kit chart packaged with indoor unit.

Leak Testing (Nitrogen or Nitrogen-Traced)

To avoid the risk of fire or explosion, never use oxygen, high
pressure air or flammable gases for leak testing of a refrigeration
system.

Pressure test the system using dry nitrogen and soapy water to
locate leaks.  If you wish to use a leak detector, charge the system
to 10 psi using the appropriate refrigerant then use nitrogen to
finish charging the system to working pressure then apply the
detector to suspect areas. If leaks are found, repair them. After
repair, repeat the pressure test. If no leaks exist, proceed to sys-
tem evacuation.

System Evacuation

Condensing unit liquid and suction valves are closed to contain
the charge within the unit.  The unit is shipped with the valve
stems closed and caps installed.  Do not open valves until the
system is evacuated.

NOTE:  Scroll compressors should never be used to evacuate or
pump down a heat pump or air conditioning system.

Prolonged operation at suction pressures less than 20 psig for

more than 5 seconds will result in overheating of the scrolls and

permanent damage to the scroll tips, drive bearings and internal

seal.

CAUTION

1. Connect the vacuum pump with 250 micron capability to the

service valves.

2. Evacuate the system to 250 microns or less using suction

and liquid service valves.  Using both valves is necessary as
some compressors create a mechanical seal separating the
sides of the system.

3. Close pump valve and hold vacuum for 10 minutes.  Typi-

cally pressure will rise during this period.

Summary of Contents for DZ13SC

Page 1: ...e is delivered at the specified airflow See outdoor unit specification sheet for split system models or product specifica tion sheet for packaged and light commercial models Specifica tion sheets can be found at www daikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be insta...

Page 2: ...on in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pump unit bases have cutouts under the outdoor coil that permit drainage of frost accumulation Situatetheunittopermitfreeunobstructeddrainage of the defrost water and ice In more severe weather locations it is recommended that the unit be elevated to allow unobstructed drainage and air flow ...

Page 3: ... or TP 107 Long Line Set Application R 410A or contact your dis tributor for assistance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4 3 8 2 1 2 5 8 1 4 3 4 3 8 7 8 3 8 3 3 4 3 8 7 8 3 8 1 1 8 3 8 3 1 2 7 8 3 8 1 1 8 3 8 1 1 8 3 8 4 7 8 3 8 1 1 8 3 8 1 1 8 3 8 5 7 8 3 8 1 1 8 3 8 1 1 8 3 8 Line Diameter In OD RECOMMENDED INTERCONNECTING TUBING Ft 0 24...

Page 4: ...ially important on suction line filter driers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart pa...

Page 5: ...allation instructions supplied with the indoor furnace air handler for spe cific wiring connections and indoor unit configuration Likewise consult the instructions packaged with the thermostat for mount ing and location information Overcurrent Protection The following overcurrent protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time ...

Page 6: ...il it may be necessary to add or remove refrigerant to attain proper charge If line set exceeds 15 feet in length refrigerant should be added at 6 ounces per foot of liquid line NOTE Charge should always be checked using superheat when using a piston and subcooling when using TXV equipped indoor coil to verify proper charge Open the suction service valve first If the liquid service valve is opened...

Page 7: ...res to stabilize then check subcooling and or superheat as detailed in the following sec tions Superheat Suct Line Temp Sat Suct Temp Subcooling Sat Liquid Temp Liquid Line Temp To prevent personal injury carefully connect and disconnect manifold gauge hoses Escaping liquid refrigerant can cause burns Do not vent refrigerant into the atmosphere Recover all refrigerant during system repair and befo...

Page 8: ... n a 123 445 n a 125 475 n a 130 500 n a 134 525 n a 138 550 n a 142 575 n a 145 600 n a 149 625 n a 152 SATURATED LIQUID PRESSURE TEMPERATURE CHART SATURATED LIQUID TEMPERATURE ºF SUCTION PRESSURE PSIG R 22 R 410A 50 26 1 52 28 3 54 29 4 56 31 6 58 32 7 60 34 8 62 35 10 64 37 11 66 38 13 68 40 14 70 41 15 72 42 16 74 44 17 76 45 19 78 46 20 80 48 21 85 50 24 90 53 26 95 56 29 100 59 31 110 64 36 ...

Page 9: ... 7 to 9 ºF and superheat of 7 to 9 ºF a If subcooling and superheat are low adjust TXV to 7 to 9 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 7 to 9 ºF then check superheat c If subcooling and superheat are high adjust TXV valve ...

Page 10: ...ltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Remove Restriction Replace Restricted Part Open Element or Limit on Elec Heater Test Heater Element and Controls Dirty Air Filter Inspect ...

Page 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 12: ...ep the outdoor coil clean Dirt leaves or debris could also restrict the airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refriger ant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a conde...

Reviews: