background image

2

Another important consideration in selecting a location for the
unit(s) is the angle to obstructions.  Either side adjacent the valves
can be placed toward the structure provided the side away from
the structure maintains minimum service clearance.  Corner in-
stallations are strongly discouraged.

Model Type

A

B

C

AA

Residential

10"

10"

18"

20"

Light Commercial

12"

12"

18"

24"

Minimum Airflow Clearance

This unit can be located at ground floor level or on flat roofs. At
ground floor level, the unit must be on a solid, level foundation
that will not shift or settle. To reduce the possibility of sound
transmission, the foundation slab should not be in contact with
or be an integral part of the building foundation. Ensure the foun-
dation is sufficient to support the unit. A concrete slab raised
above ground level provides a suitable base.

Rooftop Installations

If it is necessary to install this unit on a roof structure, ensure the
roof structure can support the weight and that proper consider-
ation is given to the weather-tight integrity of the roof. Since the
unit can vibrate during operation, sound vibration transmission
should be considered when installing the unit. Vibration absorb-
ing pads or springs can be installed between the condensing unit
legs or frame and the roof mounting assembly to reduce noise
vibration.

NOTE: These units require special location consideration in areas
of heavy snow accumulation and/or areas with prolonged
continuous subfreezing temperatures. Heat pump unit bases have
cutouts under the outdoor coil that permit drainage of frost
accumulation. Situate the unit to permit free unobstructed drainage
of the defrost water and ice.

In more severe weather locations, it is recommended that the unit
be elevated to allow unobstructed drainage and air flow. The
following elevation minimums are recommended:

Design Temperature

Suggested

Minimum Elevation

+15° and above

2 1/2"

-5° to +14°

8"

below -5°

12"

Safe Refrigerant Handling

While these items will not cover every conceivable situation, they
should serve as a useful guide.

To avoid possible injury, explosion or death, practice safe
handling of refrigerants.

To avoid possible explosion:

  Never apply flame or steam to a refrigerant cylinder. If you
     must heat a cylinder for faster charging, partially immerse

     it in warm water.

Never fill a cylinder more than 80% full of liquid refrigerant.

•   Never add anything other than R-22 to an R-22 cylinder or
     R-410A to an R-410A cylinder. The service equipment used
     must be listed or certified for the type of refrigerant used.

•   Store cylinders in a cool, dry place. Never use a cylinder
     as a platform or a roller.

•  

•   

To avoid possible explosion, use only returnable (not disposable)

service cylinders when removing refrigerant from a system.

 •  Ensure the cylinder is free of damage which could lead to a

     leak or explosion.

•   Ensure the hydrostatic test date does not exceed 5 years.

•   Ensure the pressure rating meets or exceeds 400 lbs.

When in doubt, do not use cylinder.

Summary of Contents for DZ13SC

Page 1: ...e is delivered at the specified airflow See outdoor unit specification sheet for split system models or product specifica tion sheet for packaged and light commercial models Specifica tion sheets can be found at www daikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be insta...

Page 2: ...on in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pump unit bases have cutouts under the outdoor coil that permit drainage of frost accumulation Situatetheunittopermitfreeunobstructeddrainage of the defrost water and ice In more severe weather locations it is recommended that the unit be elevated to allow unobstructed drainage and air flow ...

Page 3: ... or TP 107 Long Line Set Application R 410A or contact your dis tributor for assistance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4 3 8 2 1 2 5 8 1 4 3 4 3 8 7 8 3 8 3 3 4 3 8 7 8 3 8 1 1 8 3 8 3 1 2 7 8 3 8 1 1 8 3 8 1 1 8 3 8 4 7 8 3 8 1 1 8 3 8 1 1 8 3 8 5 7 8 3 8 1 1 8 3 8 1 1 8 3 8 Line Diameter In OD RECOMMENDED INTERCONNECTING TUBING Ft 0 24...

Page 4: ...ially important on suction line filter driers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart pa...

Page 5: ...allation instructions supplied with the indoor furnace air handler for spe cific wiring connections and indoor unit configuration Likewise consult the instructions packaged with the thermostat for mount ing and location information Overcurrent Protection The following overcurrent protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time ...

Page 6: ...il it may be necessary to add or remove refrigerant to attain proper charge If line set exceeds 15 feet in length refrigerant should be added at 6 ounces per foot of liquid line NOTE Charge should always be checked using superheat when using a piston and subcooling when using TXV equipped indoor coil to verify proper charge Open the suction service valve first If the liquid service valve is opened...

Page 7: ...res to stabilize then check subcooling and or superheat as detailed in the following sec tions Superheat Suct Line Temp Sat Suct Temp Subcooling Sat Liquid Temp Liquid Line Temp To prevent personal injury carefully connect and disconnect manifold gauge hoses Escaping liquid refrigerant can cause burns Do not vent refrigerant into the atmosphere Recover all refrigerant during system repair and befo...

Page 8: ... n a 123 445 n a 125 475 n a 130 500 n a 134 525 n a 138 550 n a 142 575 n a 145 600 n a 149 625 n a 152 SATURATED LIQUID PRESSURE TEMPERATURE CHART SATURATED LIQUID TEMPERATURE ºF SUCTION PRESSURE PSIG R 22 R 410A 50 26 1 52 28 3 54 29 4 56 31 6 58 32 7 60 34 8 62 35 10 64 37 11 66 38 13 68 40 14 70 41 15 72 42 16 74 44 17 76 45 19 78 46 20 80 48 21 85 50 24 90 53 26 95 56 29 100 59 31 110 64 36 ...

Page 9: ... 7 to 9 ºF and superheat of 7 to 9 ºF a If subcooling and superheat are low adjust TXV to 7 to 9 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 7 to 9 ºF then check superheat c If subcooling and superheat are high adjust TXV valve ...

Page 10: ...ltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Remove Restriction Replace Restricted Part Open Element or Limit on Elec Heater Test Heater Element and Controls Dirty Air Filter Inspect ...

Page 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 12: ...ep the outdoor coil clean Dirt leaves or debris could also restrict the airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refriger ant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a conde...

Reviews: