background image

3

EPA Regulations

Important: The United States Environmental 

Protection Agency (EPA) has issued various 

regulations regarding the introduction and 

disposal of refrigerants in this unit. Failure 

to follow these regulations may harm the 

environment and can lead to the imposition 

of substantial fines. Because regulations may 

vary due to passage of new laws, we suggest a 

certified technician perform any work done on 

this unit. Should you have any questions please 

contact the local office of the EPA.

National Codes

This product is designed and manufactured to permit  

installation in accordance with National Codes. It is the 

installer’s responsibility to install the product in accordance 

with National Codes and/or prevailing local codes and 

regulations.

The heating and cooling capacities of the unit should be 

greater than or equal to the design heating and cooling 

loads of the area to be conditioned. The loads should be 

calculated by an approved method or in accordance with 

ASHRAE Guide or Manual J - Load Calculations published 

by the Air Conditioning Contractors of America.

Obtain from:

American National Standards Institute 

www.ansi.org

System design and installation should also, where 

applicable, follow information presented in accepted 

industry guides such as the ASHRAE Handbooks. The 

manufacturer assumes no responsibility for equipment 

installed in violation of any code or regulation. The 

mechanical installation of the packaged roof top units 

consists of making final connections between the unit and 

building services; supply and return duct connections; and 

drain connections (if required). The internal systems of 

the unit are completely factory-installed and tested prior to 

shipment.

Units are generally installed on a steel roof mounting 

curb assembly which has been shipped to the job site for 

installation on the roof structure prior to the arrival of the 

unit. The model number shown on the unit’s identification 

plate identifies the various components of the unit such as 

refrigeration tonnage, heating output and voltage.

Carefully inspect the unit for damage including damage 

to the cabinetry. Any bolts or screws which may have 

loosened in transit must be re-tightened.  

In the event of damage, the receiver should:

1.  Make notation on delivery receipt of any visible 

damage to shipment or container.

2.  Notify carrier promptly and request an inspection.

3.  In case of concealed damage, carrier should be 

notified as soon as possible-preferably within 5 days.

4.  File the claim with the following supporting 

documents:

a.  Original Bill of Lading, certified copy, or 

indemnity bond.

b.  Original paid freight bill or indemnity in lieu 

thereof. 

c.  Original invoice or certified copy thereof, 

showing trade and other discounts or 

reductions.

d.  Copy of the inspection report issued by carrier 

representative at the time damage is reported 

to the carrier. The carrier is responsible for 

making prompt inspection of damage and for 

a thorough investigation of each claim. The 

distributor or manufacturer will not accept 

claims from dealers for transportation damage.

NOTE: When inspecting the unit for 

transportation damage, remove all packaging 

materials. Recycle or dispose  of the packaging 

material according to local codes.

Pre-Installation Checks

Carefully read all instructions for the installation prior 

to installing unit. Ensure each step or procedure is 

understood and any special considerations are taken into 

account before starting installation. Assemble all tools, 

hardware and supplies needed to complete the installation. 

Some items may need to be purchased locally.

UNIT LOCATION

WARNING

To prevent possible equipment damage, property damage, 

personal injury or death, the following bullet points must 

be observed when installing the unit. 

IMPORTANT NOTE: Remove wood shipping rails 

prior to installation of the unit.

All Installations:

IMPORTANT NOTE: 

Unit should be energized 24 

hours prior to compressor start up to ensure 

crankcase heater has sufficiently warmed the 

compressors. Compressor damage may occur if 

this step is not followed.

NOTE:  Appliance is shipped from factory for 

vertical duct application. 

Proper installation of the unit ensures trouble-free 

operation. Improper installation can result in problems 

ranging from noisy operation to property or equipment 

damages, dangerous conditions that could result in injury 

or personal property damage and that are not covered by 

the warranty. Give this booklet to the user and explain it’s 

provisions. The user should retain these instructions for 

future reference.

Summary of Contents for DFC0361D

Page 1: ...rsonnel that have been trained to install adjust service or repair hereinafter service the equipment specified in this manual should service the equipment The manufacturer will not be responsible for...

Page 2: ...any part has been under water Immediately call a qualified service technician to inspect the furnace and to replace any part of the control system and any gas control having been under water WARNING...

Page 3: ...transit must be re tightened In the event of damage the receiver should 1 Make notation on delivery receipt of any visible damage to shipment or container 2 Notify carrier promptly and request an insp...

Page 4: ...r or architect Do not skid or slide on any surface as this may damage unit base The unit must be stored on a flat level surface Protect the condenser coil because it is easily damaged Roof Curb Instal...

Page 5: ...sure gasket has been applied properly Gasket should be firmly applied to the top of the curb perimeter duct flanges and any exposed duct connection frame If gasket is loose re apply using strong weath...

Page 6: ...curb prior to installing the unit Ductwork dimensions are shown in Roof Curb Installation Instructions Refer to the Roof Curb Installation Instructions for proper curb installation Curbing must be in...

Page 7: ...t be done in accordance with these instructions the latest edition of the National Electrical Code ANSI NFPA 70 and all local codes and ordinances The unit is factory wired for the voltage shown on th...

Page 8: ...denser end of unit or through the roof curb Install conduit connectors at the desired entrance locations External connectors must be weatherproof All holes in the unit base must be sealed including th...

Page 9: ...on CONDENSATE DRAIN CONNECTION Condensate Drain Connection A 3 4 female NPT drain connection is supplied on the end of the unit and bottom of the drain pan for condensate piping An external trap must...

Page 10: ...ect installation The unit and curb assembly should be level Inspect the flashing of the roof mounting curb to the roof especially at the corners for good workmanship Also check for leaks around gasket...

Page 11: ...HEAT BR X X X X X X X X INDOOR MOTOR TAPS T1 T2 T3 T4 T5 T1 T2 T3 T4 T5 FAN GR X X COOLING STG1 YL X X COOLING STG2 PU X X X X X X HIGH HEAT BR X X X X X X RECOMMENDED SPEED TAPS 3 5T HIGH STATIC RECO...

Page 12: ...ostat at the appropriate setting for cooling and heating or automatic changeover for normal use 14 Be sure the Owner is instructed on the unit operation filter servicing correct thermostat operation e...

Page 13: ...t shut down periods where corrosive deposits accumulate on the MCHE Cleaning Procedure Relative to tube fin heat exchangers MicroChannel heat exchanger coils tend to accumulate more dirt on the surfac...

Page 14: ...ying and prevent pooling Daikin recommends a quarterly cleaning of the coils as the minimum The cleaning frequency should be increased depending on the level of dirt dust accumulation and the environm...

Page 15: ...05 321 0 35 0 6 1315 845 334 0 37 0 7 1260 880 348 0 38 0 8 1205 920 360 0 40 T5 DFC0361D DFC0363D DOWNSHOT T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1110 505 85 0 09 0 2 925 540 100 0 10 0...

Page 16: ...810 322 0 35 0 6 1325 845 334 0 37 0 7 1275 875 346 0 38 0 8 1230 910 357 0 39 T4 DFC0364D DFC0367D DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 965 485 81 0 09 0 2 895 545 89 0 10 0...

Page 17: ...1200 605 0 69 1 7 1085 1230 617 0 70 1 8 1040 1260 631 0 72 T5 T4 DFC0363W DFC0364W DFC0367W DOWNSHOT T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1500 955 474 0 53 0 9 1455 985 486 0 54 1 0 141...

Page 18: ...220 614 0 70 1 7 1070 1250 626 0 71 1 8 1025 1280 640 0 73 T5 DFC0363W DFC0364W DFC0367W HORIZONTAL T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1480 970 481 0 54 0 9 1435 1000 493 0 55 1 0 13...

Page 19: ...570 0 64 0 6 1755 960 585 0 66 0 7 1710 990 601 0 68 0 8 1650 1020 622 0 70 T4 DFC0481D DFC0483D DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1235 610 185 0 19 0 2 1170 660 195 0 20...

Page 20: ...541 0 60 0 6 1720 955 556 0 62 0 7 1670 990 573 0 64 0 8 1620 1015 589 0 66 T5 T4 DFC0484D DFC0487D DOWNSHOT T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1250 615 179 0 19 0 2 1195 660 191 0 20...

Page 21: ...285 952 1 08 1 7 1545 1310 967 1 10 1 8 1510 1325 980 1 11 T4 DFC0483W DFC0484W DFC0487W DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1750 1040 664 0 74 0 9 1695 1070 680 0 76 1 0 164...

Page 22: ...1 1 11 1 7 1530 1350 996 1 13 1 8 1495 1365 1009 1 14 T5 DFC0483W DFC0484W DFC0487W HORIZONTAL T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1735 1070 684 0 76 0 9 1680 1100 700 0 79 1 0 1625 1...

Page 23: ...0 94 0 8 2000 1090 850 0 97 0 9 1950 1115 864 0 99 1 0 1895 1145 882 1 01 T1 T2 T3 DFC0601D DFC0603D DOWNSHOT T4 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1520 705 299 0 32 0 2 1460 750 314 0 34 0...

Page 24: ...2 0 96 0 8 2005 1095 849 0 98 0 9 1960 1120 865 1 00 1 0 1915 1140 883 1 02 DFC0604D DFC0607D DOWNSHOT T1 T2 T3 T4 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1540 705 288 0 31 0 2 1485 740 302 0 32 0...

Page 25: ...365 1222 1 31 1 9 1845 1380 1240 1 32 2 0 1810 1400 1256 1 34 DFC0603W DFC0604W DFC0607W DOWNSHOT T1 T3 T2 T5 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1950 1085 812 0 85 0 9 1920 1105 830 0 87 1 0...

Page 26: ...5 1259 1 35 1 9 1825 1420 1277 1 36 2 0 1790 1440 1294 1 38 T4 T5 DFC0603W DFC0604W DFC0607W HORIZONTAL T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1930 1115 836 0 88 0 9 1900 1140 855 0 90 1 0...

Page 27: ...0 6 2290 1080 932 1 03 0 7 2255 1100 947 1 05 0 8 2220 1120 963 1 07 T4 DFC0723D DFC0724D DFC0727D DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1995 790 452 0 49 0 2 1960 815 466 0 5...

Page 28: ...75 1400 1678 1 76 1 7 2345 1420 1699 1 78 1 8 2310 1440 1720 1 81 T5 T4 DFC0723W DFC0724W DFC0727W DOWNSHOT T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 6 2280 1085 980 1 02 0 7 2240 1110 1000 1 05...

Page 29: ...1450 1745 1 82 1 7 2310 1470 1767 1 85 1 8 2275 1490 1789 1 87 T5 DFC0723W DFC0724W DFC0727W HORIZONTAL T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 6 2245 1125 1019 1 06 0 7 2205 1150 1040 1 0...

Page 30: ...20 18 2 20 4 3 23 5 25 0 5 18 8 20 4 3 0 5 24 2 25 25 7 30 4 3 31 1 35 0 5 26 3 30 4 3 0 5 31 7 35 10 2 15 4 3 14 5 20 0 5 10 7 15 4 3 0 5 15 20 10 6 15 4 3 16 20 0 5 11 3 15 4 3 0 5 16 6 20 18 2 20 4...

Page 31: ...5 47 5 53 2 50 60 9 6 8 7 1 7 1 5 59 5 64 1 60 70 58 1 66 1 60 70 9 6 8 7 70 1 77 0 80 80 1 7 1 5 60 2 68 0 70 70 9 6 8 7 1 7 1 5 72 2 78 8 80 80 11 15 4 3 15 3 20 0 5 11 5 15 4 3 0 5 15 8 20 11 15 4...

Page 32: ...0 39 9 50 50 29 7 29 7 45 45 9 6 8 7 39 3 38 4 50 50 1 7 1 5 31 4 31 2 45 45 9 6 8 7 1 7 1 5 41 0 39 9 50 50 35 7 39 7 45 45 9 6 8 7 47 7 50 6 50 60 1 7 1 5 37 8 41 6 45 45 9 6 8 7 1 7 1 5 49 8 52 4 5...

Page 33: ...5 45 9 6 8 7 1 7 1 5 49 8 52 4 50 60 48 7 54 7 50 60 9 6 8 7 60 7 65 6 70 70 1 7 1 5 50 8 56 6 60 60 9 6 8 7 1 7 1 5 62 8 67 5 70 70 61 5 69 5 70 70 9 6 8 7 73 5 80 3 80 90 1 7 1 5 63 6 71 3 70 80 9 6...

Page 34: ...16 5 20 12 4 15 3 5 15 9 20 0 6 13 15 3 5 0 6 16 5 20 16 8 20 3 5 21 2 25 0 6 17 5 20 3 5 0 6 21 9 25 22 8 25 3 5 27 2 30 0 6 23 5 25 3 5 0 6 27 9 30 28 8 30 3 5 33 2 35 0 6 29 6 30 3 5 0 6 33 9 35 40...

Page 35: ...47 5 8 73 3 8 MODEL SIZE DIM A 3 TON 39 7 8 4 TON 39 7 8 5 TON 39 7 8 6 TON 43 1 2 Horizontal Discharge 5 6 3 16 7 3 8 SUPPLY 12 X 17 RETURN 11 X 25 4 1 2 5 7 8 7 5 8 19 1 2 27 3 4 5 5 16 47 9 16 7 1...

Page 36: ...6 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S06 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S06 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S32 30 EH D S06 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S3...

Page 37: ...FLOAT SWITCH OR SMOKE DETECTOR IS INSTALLED UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE IF MULTIPLE SAFETIES ARE INSTALLED PLUG IN THE ADDITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SA...

Page 38: ...L DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT...

Page 39: ...RE INSTALLED PLUG IN THE ADDITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND...

Page 40: ...INSTALLED PLUG IN THE ADDITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIR...

Page 41: ...41...

Page 42: ...42...

Page 43: ...43 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 44: ...2021 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikincom...

Reviews: