IM 782-12 • DESTINY AIR HANDLERS 30 www.DaikinApplied.com
Physical Data
Fan Data
Table 17: Forward Curved Fan Data
Unit size
002
003
004
005
007
010
015
020
025
030
Fan type
DWDI FC
DWDI FC
DWDI FC
DWDI FC
DWDI FC
DWDI FC
Twin DWDI
FC
Twin DWDI
FC
Twin DWDI
FC
Twin DWDI
FC
Diameter
7/7
9/9
9/9
10/10
12/12
12/12
10/10
12/12
15/15
15/15
HP range
0.50–2
0.50–3
0.5–5
0.75–5
1–5
1–7.5
2–15
3–15
5–20
5–20
cfm minimum
fan limit
206
206
529
529
765
765
1059
1529
2118
2118
cfm maximum
fan limit
2,088
2,088
5,765
6,176
8,529
8,529
12,353
17,059
26,706
26,706
Maximum rpm
2,680
2,650
2,650
2,100
1,700
1,700
2,100
1,700
1,500
1,500
Class
1
1
1
1
1
1
1
1
1
1
Motor sheave
VP, VL, VM
VP, VL, VM
VP, VL, VM
VP, VL, VM
VP, VL, VM
VP, VL, VM
VP, VL, VM
VP, VL, VM
VP, VL, VM
VP, VL, VM
Fan sheave
AK, BK
AK, BK
AK, BK
AK, BK
AK, BK
AK, BK
AK, BK
AK, BK
AK, BK
AK, BK
Belt
A, AX, B, BX A, AX, B, BX A, AX, B, BX A, AX, B, BX A, AX, B, BX A, AX, B, BX A, AX, B, BX A, AX, B, BX A, AX, B, BX A, AX, B, BX
Fan shaft diameter
3/4ʺ
3/4ʺ
3/4ʺ
3/4ʺ
1.0ʺ
1.0ʺ
3/4ʺ
1.0ʺ
1.0ʺ
1.0ʺ
Weight—lbs (kg)
19.03
(8.63)
33.95
(15.40)
33.95
(15.40)
41.45
(18.80)
60.85
(27.60)
60.85
(27.60)
79.37
(36.00)
126.77
(57.50)
154.87
(70.25)
154.87
(70.25)
Table 18: Plenum Fan Data
Unit size
002
003
004
005
007
010
015
020
025
030
Fan type
SWSI DD
Plenum
SWSI DD
Plenum
SWSI DD
Plenum
SWSI DD
Plenum
SWSI DD
Plenum
SWSI DD
Plenum
SWSI DD
Plenum
SWSI DD
Plenum
SWSI DD
Plenum
SWSI DD
Plenum
Diameter (in)
9
10
11
12.5
14
16
20
22
25
25
HP range
1.5–2
1.5–5
1–5
1–5
1–7.5
1–7.5
1.5–15
2–15
5–20
5–20
cfm minimum
fan limit
100
150
200
200
250
325
525
650
800
800
cfm maximum
fan limit
1800
2650
4100
4100
5000
5200
9200
12,900
16,150
16,150
Maximum rpm
5175
5175
4245
4245
3600
2625
2265
2310
2060
2060
Weight with smallest
motor—lbs (kg)
50 (22.7)
57 (25.9)
59 (26.8)
62 (28.1)
71 (32.2)
86 (39)
147 (66.7)
176 (79.8)
263 (119.3)
263 (119.3)
Weight with largest
motor—lbs (kg)
56 (25.4)
84 (38.1)
86 (39)
89 (40.4)
114 (51.7)
154 (69.9)
281 (127.4) 312 (141.5) 363 (164.7) 363 (164.7)
Filter Data
Table 19: Filter Data
Unit size
002
003
004
005
007
010
015
020
025
030
Flat filters
Flat filter bank number
1
1
1
1
1
1
2
2
2
2
Flat filter (qty) size
(1) 16 × 25 (1) 18 × 24 (2) 16 × 20 (2) 20 × 24 (2) 24 × 24 (3) 20 × 25 (3) 12 × 24
(3) 24 × 24 (6) 24 × 24
(4) 20 × 24
(4) 24 × 24
(6) 16 × 25
(4) 20 × 25
Flat filter depth options
2ʺ, 4ʺ
2ʺ, 4ʺ
2ʺ, 4ʺ
2ʺ, 4ʺ
2ʺ, 4ʺ
2ʺ, 4ʺ
2ʺ, 4ʺ
2ʺ, 4ʺ
2ʺ, 4ʺ
2ʺ, 4ʺ
Angular filters
Angular filter bank number
1
1
1
2
2
2
2
3
3
3
Angular filter (qty) size
(1) 20 × 24 (2) 16 × 20 (2) 20 × 20 (4) 16 × 20 (4) 16 × 25 (6) 16 × 20 (6) 20 × 24 (9) 20 × 24 (6) 20 × 24
(6) 24 × 24
(6) 20 × 24
(6) 24 × 24
Angular filter depth options
2ʺ
2ʺ
2ʺ
2ʺ
2ʺ
2ʺ
2ʺ
2ʺ
2ʺ
2ʺ