44
Installation Manual 3P291714-7H
DCM601B51 intelligent Touch Manager
English
5.2
Steps for setting the outdoor unit Airnet address
1. Press the BS1 button for 5 seconds or more.
The LEDs and segments will be in the state shown below.
LED (segment) display
LED display’s outdoor unit
Segment display’s
outdoor unit
H1P
H2P
H3P
H4P
H5P
H6P
H7P SEG1 SEG2 SEG3
2
0
0
2.
Press the BS2 button 13 times. (Select the setting value.)
3.
Press the BS3 button. You can now confirm the current Airnet address setting by the
LED (segment).
4. Press the BS2 button to change to any Airnet address.
(Set the Airnet address number within the range of 1 to 63.)
5.
Press the BS3 button 2 times to fix the Airnet address setting.
6. Press the BS1 button 1 time to return to the normal mode.
5.3
Setting items LED (segment) display
When you press the BS2 button and select setting items, the LED (segment) display will
be in the state shown below.
Setting items
LED display’s outdoor unit
Segment display’s
outdoor unit
H1P H2P H3P H4P H5P H6P H7P SEG1
SEG2
SEG3
Demand address
setting
2
0
2
Demand setting enabled/
disabled
2
1
2
Outdoor unit
Airnet address setting
2
1
3