Installer Setup
26
Dry Contact Use (Setup step 28)
Condensate Pan -
If selected when the
Dry Contact is active, the thermostat will
lockout compressor terminal(s) and
“CONDENSATE PAN” will appear on
the display.
Holiday
- If Holiday is selected when the dry contact is active, the
thermostat will be forced into HOLIDAY/ Unoccupied settings.
FDD -
If FDD is selected when the dry contact is active, “EQUIP
FAULT” will appear on the display.
Occupied -
If Occupied is selected when the dry contact is active,
the thermostat will be forced into occupied settings.
Dry Contact Operation
Dry Contact Polarity (Setup step 27)
Open (Normally Open)
- The dry contact is open
until the connected device closes the circuit.
Closed (Normally Closed)
- The dry contact is
closed until the connected device opens the circuit.