17
|
Electrical installation
Installer and user reference guide
64
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P602817-1A – 2020.05
Tightening torques
Wiring
Screw size
Tightening torque
(N•m)
Power supply cable
M4
1.2~1.4
Transmission cable (F1, F2)
M3.5
0.8~0.9
User interface cable
▪
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
17.1.3 Specifications of standard wiring components
Component
Class
50
71
112
Power supply
cable
MCA
(a)
1.4 A
2.0 A
2.9 A
Voltage
220~240 V
Phase
1~
Frequency
50/60 Hz
Wire sizes
2.5 mm
2
(3‑core wire)
H07RN-F (60245 IEC 66)
Transmission wiring
0.75 to 1.25 mm² (2‑core wire)
H05RN-F (60245 IEC 57)
indoor↔outdoor - maximum 1000 m (total
wiring length 2000 m)
indoor↔user interface - maximum 500 m
User interface cable
Recommended field fuse
16 A
Residual current circuit
breaker
Must comply with applicable legislation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of
combination with indoor units for exact values).
17.2 To connect the electrical wiring to the indoor unit
NOTICE
▪
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
▪
For instructions on how to connect the optional equipment, see the installation
manual delivered with the optional equipment.
▪
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
It is important to keep the power supply and the transmission wiring separated
from each other. In order to avoid any electrical interference the distance between
both wirings should ALWAYS be at least 50 mm.