Operation manual

8

4P563995-1 2019.01

BRC7FA532F(B) + BRC7FB532F(B)

Wireless remote controller kit

Press OPERATION MODE SELECTOR button.
" " on the left-hand of the malfunction code blinks.

Press  PROGRAMMING  TIMER  button  and  change
the malfunction code.
Press until the indoor unit beeps twice.

Press OPERATION MODE SELECTOR button .
" " on the right-hand of the malfunction code blinks.

Press  PROGRAMMING  TIMER  button  and  change
the malfunction code.
Press until the indoor unit makes a long beep.
The  malfunction  code  is  fixed  when  the  indoor  unit
makes a long beep.

Press OPERATION MODE SELECTOR button to get
the display back to its normal state.

In case besides emergency stop

1

The unit does not operate at all.

Check  if  the  receiver  is  exposed  of  sunlight  or
strong light. Keep receiver away from light.

Check  if  there  are  batteries  in  the  remote
controller. Place the batteries.

Check  if  the  indoor  unit  number  and  wireless
remote controller number are equal. See figure 6.
Operate the indoor unit with the remote controller
of the same number.
Signals transmitted from a remote controller of a
different  number  cannot  be  accepted.  (If  the
number is not mentioned, it is considered as "1".)

2

The system operates but it does not sufficiently cool
or heat.

If the set temperature is not proper.

If the FAN SPEED is set to LOW SPEED.

If the air flow angle is not proper.

Contact the place of purchase in the following case.

Trouble

The RUN lamp of the indoor unit is flashing and the unit
does not work at all. See figure 7.

Remedial action

Check  the  malfunction  code  (

a1

-

if

)  on  the  remote

controller.
Notify  and  inform  the  model  name  and  what  the
malfunction code indicates to your dealer.

Not malfunction of the air conditioner 

The  following  symptoms  do  not  indicate  air  conditioner
malfunction:

Symptom 1: The system does not operate

3

4

5

6

7

Reset of the display. 

When  you  detect  a  burning  odor,  shut  OFF
power  immediately  and  contact  the  place  of
purchase. Using the equipment in anything but
proper  working  condition  can  result  in
equipment damage, electric shock and/or fire.

1

Malfunction code

2

Unit No. which sensed trouble

3

INSPECTION display

Example

Reason

The system does not 
restart immediately after 
the ON/OFF button is 
pressed.

If the OPERATION lamp 
lights, the system is in 
normal condition. It does 
not restart immediately 
because a safety device 
operates to prevent 
overload of the system.
After 3 minutes, the 
system will turn on again 
automatically.

The system does not 
restart immediately when 
TEMPERATURE 
SETTING button is 
returned to the former 
position after pushing the 
button.

It does not restart 
immediately because a 
safety device operates to 
prevent overload of the 
system.
After 3 minutes, the 
system will turn on again 
automatically.

If the reception beep is 
rapidly repeated 3 times 
(It sounds only twice 
when operating normally.)

Control is set to the 
optional controller for 
centralized control.

If the defrost lamp on the 
indoor unit's display is lit 
when heating is started.

This indication is to warn 
against cold air being 
blown from the unit. 
There is nothing wrong 
with the equipment.

The outdoor unit stops.

Because the room 
temperature reaches to 
the set temperature. The 
indoor unit goes into fan 
operation.

4PEN563995-1.book  Page 8  Friday, January 25, 2019  12:21 PM

Summary of Contents for BRC7FA532FB

Page 1: ...OPERATION MANUAL BRC7FA532F BRC7FA532FB BRC7FB532F BRC7FB532FB Wireless remote controller kit 4PEN563995 1 book Page 1 Friday January 25 2019 12 21 PM...

Page 2: ...N TIME TEMP UP DOWN CANCEL RESERVE TIMER MODE 5 7 24 25 9 8 10 17 16 14 15 12 13 11 22 23 21 18 19 2 1 1 2 3 4 6 1 2 3 UNITNO CODE UNITNO MODE TIMER RESERVECANCEL DOWN UP TEST SWING FAN TIME TEMP ON O...

Page 3: ...re electric shocks or fire hazards Do not attempt to install or repair the air conditioner yourself Improper workmanship may result in water leakage electric shocks or fire hazards Please contact your...

Page 4: ...elect OPERATION MODE 16 FILTER SIGN RESET BUTTON Refer to the section of MAINTENANCE in the operation manual attached to the indoor unit 17 INSPECTION TEST OPERATION BUTTON This button is used only by...

Page 5: ...g the remote controller in the remote controller holder Install the remote controller holder to a wall or a pillar with the attached screw Make sure the remote controller transmits How to put the batt...

Page 6: ...operation DRY operation The function of this program is to decrease the humidity in your room with the minimum temperature decrease The set point is the air temperature when starting operation by dry...

Page 7: ...ntrol the fan speed in order to protect the unit The movable limit of the flap is changeable Contact your dealer for details Up and down adjustment Press the AIR FLOW DIRECTION ADJUST button to select...

Page 8: ...stem is installed as shown below it is necessary to designate the master remote controller For Heat pump system When one outdoor unit is connected with several indoor units For Heat recovery system Wh...

Page 9: ...controls up to 16 indoor units All indoor units are equally set Two remote controller control system Two remote controllers control one indoor unit In case of group control system one group of indoor...

Page 10: ...ion code a1 if on the remote controller Notify and inform the model name and what the malfunction code indicates to your dealer Not malfunction of the air conditioner The following symptoms do not ind...

Page 11: ...and the unit stops When the noise is gone the unit automatically restarts Example Reason The indoor unit makes a PEEE receiving sound When operation changeover is under control the control is set to t...

Page 12: ...4P563995 1 2019 01 Copyright 2019 Daikin 4PEN563995 1 book Page 1 Friday January 25 2019 12 21 PM...

Reviews: