Outline of Control (Indoor Unit)
SiUS341802E
69
Functions and Control
9.2
Set Temperature and Control Temperature
9.2.1 Without Optional Infrared Presence/Floor Sensor
The relationship between remote controller set temperature and control target temperature is
described below.
•
When the suction air thermistor is used for controlling (Default), the control target temperature is
determined as follows to prevent insufficient heating in heating operation.
Control target temperature: remote controller displayed tempe 2°C (3.6°F).
•
The temperature difference for cooling
⇔
heating mode switching is 5°C (9°F).
•
The above also applies to automatic operation.
When setting the suction air thermistor (Default setting)
When using the remote controller thermistor (Field setting is required)
Examples are given to illustrate a control target temperature that satisfies the remote controller set
temperature.
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35˚C
Cooling
Heating
57.2
60.8
69.8
62.6
71.6
64.4
73.4
66.2
75.2
59
68
78.8 80.6 82.4 84.2
77
87.8 89.6 91.4 93.2 95˚F
86
Temperature
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35˚C
Cooling
Heating
57.2
60.8
69.8
62.6
71.6
64.4
73.4
66.2
75.2
59
68
78.8 80.6 82.4 84.2
77
87.8 89.6 91.4 93.2 95˚F
86
Temperature
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...