SiUS341802E
Centralized Control Group No. Setting
Remote Controller
36
4.2
Wireless Remote Controller
Group No. setting by wireless remote controller for centralized control
1. When in the normal mode, press
INSPECTION/TEST
button for 4 seconds or more to enter field setting
mode.
2. Set mode No.
00
with
MODE
button.
3. Set the group No. for each group with
UP
button or
DOWN
button.
4. Enter the selected group numbers by pressing
RESERVE
button.
5. Press
INSPECTION/TEST
button and return to the normal mode.
UP
button
DOWN
button
MODE
button
RESERVE
button
Mode No.
Field setting mode
Group No.
INSPECTION/TEST
button