Troubleshooting by Error Code
SiUS341802E
271
Service Diagnosis
2.65 Improper Combination of Indoor and Outdoor Units,
Indoor Units and Remote Controller
Error Code
UA
Applicable
Models
All indoor unit models
All outdoor unit models
Method of Error
Detection
A difference occurs in data by the type of refrigerant between indoor and outdoor units.
The number of indoor units connected is out of the allowable range.
Error Decision
Conditions
The error decision is made as soon as either of the abnormalities aforementioned is detected.
Supposed
Causes
Excess of connected indoor units
Defective outdoor unit PCB
Mismatch of the refrigerant type of indoor and outdoor unit.
Setting of outdoor unit PCB was not carried out after replacing to spare PCB.
Troubleshooting
Ensure the sub code or the lamp display of
monitor mode, and then go to the following:
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Go to Diagnosis Flowchart-1.
(Connection of excess indoor
units)
Go to Diagnosis Flowchart-2.
(Connection of incorrect models
of indoor units)
Go to Diagnosis Flowchart-3.
(Improper combination of outdoor
units)
Go to Diagnosis Flowchart-4.
(Wrong connection)
Go to Diagnosis Flowchart-6.
(Multi system combination error)
UA-17
Error code
Sub code
Error code
Sub code
Error code
Sub code
Error code
Sub code
Error code
Sub code
UA-18
UA-20
UA-21
Go to Diagnosis Flowchart-5.
(Incorrect system setup)
Error code
Sub code
UA-29
UA-35
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...