Troubleshooting by Error Code
Service Diagnosis
258
2.59 Check Operation not Executed
Error Code
U3
Applicable
Models
All outdoor unit models
Method of Error
Detection
Check operation is executed or not executed
Error Decision
Conditions
Error is decided when the unit starts operation without check operation.
Supposed
Causes
Check operation is not executed.
Troubleshooting
The contents of individual
failures vary with sub code.
Ensure the sub code, and
then go to the following:
Conduct the test operation.
(The test operation has not
been conducted.)
U3-03
Check for the refrigerant
piping, and then conduct
the test operation.
U3-04
Conduct the test operation
(due to the premature end
of the test operation).
U3-05
Conduct the test operation
(due to the premature end
of the test operation).
U3-06
Check for transmission
between indoor and
outdoor units, and then
conduct the test operation.
U3-07
Check for transmission
between indoor and
outdoor units, and then
conduct the test operation.
U3-08
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...