SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
234
2.46 Reactor Temperature Rise Abnormality
Error Code
L3
Applicable
Models
RXLQ72TATJU
Method of Error
Detection
Detect according to the value detected with the reactor surface thermistor.
Error Decision
Conditions
When the temperature detected with the reactor surface thermistor is more than the specified
temperature.
Supposed
Causes
Defective connection of harness
Defective reactor surface thermistor
Defective inverter PCB
Troubleshooting
Is
reactor
harness connected to
the terminal strip
correctly?
Is the wiring
disconnection in the
reactor surface
thermistor?
NO
YES
YES
NO
Connect the harness
correctly.
Replace the thermistor.
Replace the inverter PCB
(A3P).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.