background image

INSTALLATION 
MANUAL

R410A Split Series

Installation manual

R410A Split series

English

Installationsanleitung

Split-Baureihe R410A

Deutsch

Manuel d’installation

Série split R410A

Français

Montagehandleiding

R410A Split-systeem

Nederlands

Manual de instalación

Serie Split R410A

Español

Manuale d’installazione

Serie Multiambienti R410A

Italiano

Εγχειρίδιο

 

εγκατάστασης

∆ιαιρούμενης

 

σειράς

 R410A

Ελληνικά

Manual de Instalação

Série split R410A

Portugues

Руководство

 

по

 

монтажу

Серия

 R410A 

с

 

раздельной

 

установкой

Русский

Montaj k

ı

lavuzlar

ı

R410A Split serisi

Türkçe

Models
RXS20L3V1B
RXS25L3V1B
RXS35L3V1B
ARXS25L3V1B
ARXS35L3V1B

Summary of Contents for ARXS-L3

Page 1: ...Split systeem Nederlands Manual de instalación Serie Split R410A Español Manuale d installazione Serie Multiambienti R410A Italiano Εγχειρίδιο εγκατάστασης ιαιρούμενης σειράς R410A Ελληνικά Manual de Instalação Série split R410A Portugues Руководство по монтажу Серия R410A с раздельной установкой Русский Montaj kılavuzları R410A Split serisi Türkçe Models RXS20L3V1B RXS25L3V1B RXS35L3V1B ARXS25L3V...

Page 2: ...A e giudicato positivamente da B secondo il Certificato C 07 ȈȘȝİȓȦıȘ ȩʌȦȢ țĮșȠȡȓȗİIJĮȚ ıIJȠ A țĮȚ țȡȓȞİIJĮȚ șİIJȚțȐ Įʌȩ IJȠ B ıȪȝijȦȞĮ ȝİ IJȠ ȆȚıIJȠʌȠȚȘIJȚțȩ C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 ɉɪɢɦɟɱɚɧɢɟ ɤɚɤ ɭɤɚɡɚɧɨ ɜ A ɢ ɜ ɫɨɨɬɜɟɬɫɬɜɢɢ ɫ ɩɨɥɨɠɢɬɟɥɶɧɵɦ ɪɟɲɟɧɢɟɦ B ɫɨɝɥɚɫɧɨ ɋɜɢɞɟɬɟɥɶɫɬɜɭ C 10 Bemærk som anført i A og positivt vurderet af B i h...

Page 3: ...normal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced ...

Page 4: ...om ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side facing the wall Never install the outdoor unit at a site where the suction side may be exposed directly to wind To prevent exposure to wind it is recommended to install a b...

Page 5: ...e the stop valve cover Remove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve cover Insert the upper part of the stop valve cover into the outdoor unit to install Tighten the screws Stop valve cover Allow space for piping and electrical servicing 1 5m Min allowable piping length Be sure to add the proper amount of additional refrigerant Failure to...

Page 6: ...e foundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work 1 Use drain plug for drainage 2 If the drain port is covered by a mounting base or floor surface place additional foot bases of at ...

Page 7: ...torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches A A Cut exactly at right angles Remove burrs Set exactly at the position shown below Flaring Die Check Flare s inner surface must be flaw free The pipe end must be evenly ...

Page 8: ...ches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D 12 15mm I D 8 10mm Minimum bend radius Th...

Page 9: ... of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep ...

Page 10: ... valve cover 3 Disconnect the selective connector for standby electricity saving 4 Turn on the main power supply CAUTION Before connecting or disconnecting the selective connector for standby electricity saving make sure that the main power supply is turned off The selective connector for standby electricity saving is required if an indoor unit other than the above applicable one is connected Fill...

Page 11: ...he liquid stop valve close the gas stop valve within 3 minutes then stop the forced cooling operation Facility Setting cooling at low outdoor temperature This function is designed for facilities such as equipment or computer rooms It is never to be used in a residence or office where people occupy the space 1 Cutting jumper 9 J9 on the circuit board will expand the operation range down to 15 C How...

Page 12: ...l block Observe the notes mentioned below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal block using a single core wire be sure to perform curling Problems with the work may cause heat and fires If the stranded wires must be used make sure to use the round crimp style terminal for connectio...

Page 13: ...DB1 Diode bridge E1 E2 HL1 HN1 HR1 HR2 MR30_A MR30_B Connection E1H Heater FU1 FU2 FU3 Fuse IPM1 Intelligent power module L Live L1 Coil L1R Reactor M1C Compressor motor M1F Fan motor MR30 MRCW MRM10 Magnetic relay N Neutral PCB1 Printed circuit board PS Power supply Q1L Overload protector R1T R2T R3T Thermistor S20 S30 S40 S50 S71 S80 S90 Connector SA1 Surge arrestor V2 V3 V150 Varistor X1M Termi...

Page 14: ... a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test items Test items Symptom Check Indoor and ou...

Page 15: ......

Page 16: ...3P381941 1 2014 06 Copyright 2014 Daikin ...

Reviews: