5 Commissioning

Installation manual

11

(A)RXP20~3 RXF20~3 RXF20~25B5V1B
R32 split series
3P519299-2H – 2019.09

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

4.6.1

Specifications of standard wiring
components

Component

Power supply cable Voltage

220~240 V

Phase

1~

Frequency

50 Hz

Wire sizes

MUST comply with

applicable legislation

Interconnection cable
(indoor↔outdoor)

4-core cable ≥1.5 mm² and

applicable for 220~240 V

Recommended field fuse

16 A

Earth leakage circuit breaker

MUST comply with

applicable legislation

4.6.2

To connect the electrical wiring on the
outdoor unit

1

Remove the service cover.

2

Open the wire clamp.

3

Connect the interconnection cable and power supply as follows:

50 Hz

220-240 V

c

d

f

a

b

e

a

Interconnection cable

b

Power supply cable

c

Circuit breaker

d

Earth leakage circuit breaker

e

Power supply

f

Earth

4

Tighten  the  terminal  screws  securely.  We  recommend  using  a
Phillips screwdriver.

4.7

Finishing the outdoor unit
installation

4.7.1

To finish the outdoor unit installation

1

Insulate and fix the refrigerant piping and interconnection cable
as follows:

f

b

a

e

d

c

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Liquid pipe

e

Liquid pipe insulation

f

Finishing tape

2

Install the service cover.

4.7.2

To close the outdoor unit

NOTICE

When  closing  the  outdoor  unit  cover,  make  sure  that  the
tightening torque does NOT exceed 1.3 N•m.

2

1

1

5

Commissioning

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

5.1

Checklist before commissioning

After  the  installation  of  the  unit,  first  check  the  items  listed  below.
Once all checks are fulfilled, the unit must be closed. Power-up the
unit after it is closed.

The 

indoor unit

 is properly mounted.

Summary of Contents for ARXP20L5V1B

Page 1: ...stallation manual R32 split series English Installation manual R32 split series RXP20L5V1B RXP25L5V1B RXP35L5V1B ARXP20L5V1B ARXP25L5V1B ARXP35L5V1B RXF20A5V1B RXF25A5V1B RXF35A5V1B RXF20B5V1B RXF25B5V1B ...

Page 2: ... при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja lietoti atbilstoši ražotāja norādījumiem atbilst sekojošiem standartiem un citiem normatīviem dokumentiem sú v zhode s nasledovnou ými normou ami alebo iným i normatívnym i dokumentom ami za predpokladu že sa používa...

Page 3: ...us ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja lietoti atbilstoši ražotāja norādījumiem atbilst sekojošiem standartiem un citiem normatīviem dokumentiem sú v zhode s nasledovnou ými normou ami alebo iným i normatívnym i dokumentom ami za predpokladu že sa používajú v súlade s našim návodom ürünün talimatlarımıza göre kullanılması koşuluyla aşağıdaki s...

Page 4: ...is t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja lietoti atbilstoši ražotāja norādījumiem ...

Page 5: ...components 11 4 6 2 To connect the electrical wiring on the outdoor unit 11 4 7 Finishing the outdoor unit installation 11 4 7 1 To finish the outdoor unit installation 11 4 7 2 To close the outdoor unit 11 5 Commissioning 11 5 1 Checklist before commissioning 11 5 2 Checklist during commissioning 12 5 3 To perform a test run 12 5 4 Starting up the outdoor unit 12 6 Disposal 12 6 1 Overview Dispos...

Page 6: ...tlet b Air inlet It is recommended to install a baffle plate when the air outlet is exposed to wind It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet 3 1 2 Additional installation site requirements of the outdoor unit in cold climates Protect the outdoor unit against ...

Page 7: ...rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resistance of at least 120 C Insulation thickness Pipe outer diameter Øp Insulation inner diameter Øi Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm Øi Øi t Øp Øp If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the insulation materials should be at least 20 mm ...

Page 8: ...ing the paint field supply 4 Attach the ends of the cables and tighten them 4 3 Connecting the refrigerant piping DANGER RISK OF BURNING 4 3 1 About connecting the refrigerant piping Before connecting the refrigerant piping Make sure the outdoor and indoor unit are mounted Typical workflow Connecting the refrigerant piping involves Connecting the refrigerant piping to the indoor unit Connecting th...

Page 9: ...t vacuum or CANNOT maintain the vacuum for 1 hour do the following Check for leaks again Perform vacuum drying again NOTICE Make sure to open the stop valves after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor 4 5 Charging refrigerant 4 5 1 About charging refrigerant The outdoor unit is factory charged with re...

Page 10: ...he determined additional amount 4 5 5 To charge additional refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains fluorinated greenhouse gases Its global warming potential GWP value is 675 Do NOT vent these gases into the atmosphere When charging refrigerant ALWAYS use protective gloves and safety glasses Prerequisite Before charging refrig...

Page 11: ...mply with applicable legislation 4 6 2 To connect the electrical wiring on the outdoor unit 1 Remove the service cover 2 Open the wire clamp 3 Connect the interconnection cable and power supply as follows 50 Hz 220 240 V c d f a b e a Interconnection cable b Power supply cable c Circuit breaker d Earth leakage circuit breaker e Power supply f Earth 3 4 Tighten the terminal screws securely We recom...

Page 12: ...ter the unit is turned OFF INFORMATION Even if the unit is turned OFF it consumes electricity When the power turns back on after a power break the previously selected mode will be resumed 5 4 Starting up the outdoor unit See the indoor unit installation manual for configuration and commissioning of the system 6 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system t...

Page 13: ...h if present on the indoor unit Method 2 Using the indoor unit user interface 6 3 1 To start stop forced cooling using the indoor unit ON OFF switch 1 Press the ON OFF switch for at least 5 seconds Result Operation will start INFORMATION Forced cooling stops automatically after 15 minutes 2 To stop operation sooner press the ON OFF switch 6 3 2 To start stop forced cooling using the indoor unit us...

Page 14: ... SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOT...

Page 15: ......

Page 16: ...LERİ SAN TİC A Ş İSTANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P519299 2H 2019 09 Copyright 2019 Daikin ...

Reviews: