Main Functions
SiBE04-809
24
Function and Control
Since the set temperature is shifted by 2°C higher for 40 minutes, compressor speed
becomes low and can realize energy saving operation. But as thermostat is prone to be off
by the fact that the set temperature has been shifted, the thermostat-off action is prohibited
in 40 minutes so as to prevent this phenomena.
After this 40 minutes, the prohibition of the thermostat-off is cancelled and it can realize the
conditions to conduct thermostat-off depending on the room temperature. In or after this 40
minutes, if the sensor detects human motion detection signal, it let the set temperature and
the fan speed return to the original set point, keeping a normal operation.
Others
The dry operation can’t command the setting temperature with a remote controller, but
internally the set temperature is shifted by 1°C.
1.10
Inverter POWERFUL Operation
Outline
In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Details of the
Control
When POWERFUL button is pushed in each operation mode, the fan speed/setting temperature
will be converted to the following states in a period of 20 minutes.
Ex.) : POWERFUL operation in cooling mode.
Operation mode
Fan speed
Target set temperature
COOL
H tap + 70 rpm
18°C
DRY
Dry rotating speed +
70 rpm
Normally targeted
temperature in dry
operation; Approx.
–2.5°C
HEAT
H tap + 50 rpm
30°C
FAN
H tap + 50 rpm
—
AUTO
Same as cooling /
heating in POWERFUL
operation
The target is kept
unchanged
(R4995)
Target temp.
Fan
70rpm
Set temp.
18˚C
POWERFUL ON
POWERFUL OFF
H tap
Set tap
It should be the lower limit of cooling temperature.
It counts 20 min. also in the remote controller.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Stop
3. POWERFUL operation is OFF.
20min.
Summary of Contents for ARXG25E3V1B
Page 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series ...
Page 11: ...Introduction SiBE04 809 x ...
Page 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4 ...