
Check
SiBE04-809
120
Service Diagnosis
5.1.6
Discharge Pressure Check
Check No.08
5.1.7
Outdoor Unit Fan System Check
(With DC Motor)
Check No.09
(R7158)
Not dirty
YES
YES
Dirty
NO
NO
NO
YES
Are the heat exchanger
and air filter dirty?
Is the connection pipe
deformed?
Is the stop valve open?
High
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean.
Replace the compressor.
Discharge pressure check
(R7159)
YES
YES
NO
NO
Outdoor unit fan
system
functioning.
Check the outdoor unit fan system.
Go to
Check No. 15
.
Outdoor unit fan running?
Fan motor
lead wire connector
disconnected?
Reconnect.
Summary of Contents for ARXG25E3V1B
Page 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series ...
Page 11: ...Introduction SiBE04 809 x ...
Page 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4 ...