8
|
Electrical installation
Installer reference guide
46
(A)RXF20~42C5V1B
R32 split series
4P519439-10J – 2021.06
8.2.4 Specifications of standard wiring components
Component
Power supply cable
Voltage
220~240 V
Phase
1~
Frequency
50 Hz
Wire sizes
MUST comply with applicable
legislation
Interconnection cable (indoor↔outdoor)
4-core cable ≥1.5 mm² and
applicable for 220~240 V
Recommended field fuse
16 A
Earth leakage circuit breaker
MUST comply with applicable
legislation
8.2.5 To connect the electrical wiring to the outdoor unit
1
"6.2.2 To open the outdoor unit"
26].
2
Strip insulation (20 mm) from the wires.
a
b
a
Strip wire end to this point
b
An excessive strip length may cause electrical shock or leakage
3
Open the wire clamp.
4
Connect the interconnection cable and power supply as follows:
50 Hz
220-240 V
c
d
f
a
b
e
a
Interconnection cable
b
Power supply cable
c
Circuit breaker
d
Residual current device
e
Power supply
f
Earth
3×
5
Tighten the terminal screws securely. We recommend using a Phillips
screwdriver.