6
|
Unit installation
Installer reference guide
25
(A)RXF20~42C5V1B
R32 split series
4P519439-10J – 2021.06
a
b
c
d
c
d
a
Sea wind
b
Building
c
Outdoor unit
d
Windbreaker
The outdoor unit is designed for outdoor installation only, and for ambient
temperatures ranging from –10 to 46°C in cooling mode and from –15 to 24°C in
heating mode. Unless otherwise specified in the operation manual of the
connected indoor unit.
6.1.2 Additional installation site requirements of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
a
b
c
c
d
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
In any case, provide at least 300 mm of free space below the unit. Additionally,
make sure the unit is positioned at least 100 mm above the maximum expected
level of snow. See
"6.3 Mounting the outdoor unit"
26] for more details.
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed and a pedestal.