www.DaikinApplied.com 31
IM 1083-3
Figure 48: 4-pin plug MicroTech control wiring diagram
Communication
Module
(4-pin)
Male Connector
Unit Ventilator
Optional Building Automation System (BAS)
Wiring:
Use twisted shielded pair (Connect Air W221P-2544 or equivalent).
Daisy-chain and tie shield to earth ground at
one
point only.The polarity of the signal must always be
maintained throughout the network. Always c to + and - to -. The shield connection must be
continuous throughout the entire network and must be connected to earth ground at
one
(and only one) point.
The N2 Bus can use either solid or stranded wires of the following types:
3-wire twisted cable, 2 twisted-pair telephone cable, or two twisted pair with shield.
The wiring is polarity sensitive. The polarity of the signal must always be maintained
throughout the network. Always c to + and - to -. The shield connection must
be continuous throughout the entire network and must be connected to earth ground at
one
(and only one) point.
Use Belden 8471, NEMA Level 4, or Echelon-approved equivalent wire. Since the L
ON
W
ORKS
communication
wiring is polarity insensitive, no polarity must be observed when making connections via the unshielded twisted-pair wiring.
L
ON
W
ORKS
®
FTT–10 (A)
FTT–10 (B)
BACnet
®
GND
3
2
1
(4-pin)
Female Connector
Black
Red
GND
RT-
RT+
(By others)
(By others)
Figure 49: 10-pin plug MicroTech wiring diagram
Unit Ventilator
DO7
DO8-NO
DO8-NC
DO5
P6
Connector
Wire
Caps
UVC
601A
602A
603A
604A
605A
606A
607A
608A
609A
610A
DO8-Comm
TB2 - 24VAC Comm
DO13
24VAC+
Empty
Empty
External Output
Option 1 Device
(by Others)
Pump or Motorized
Valve
Normally Open
Factory Wiring
Field Wiring (by Others)
External Device (by Others)
External Output
Option 3 Device
(by Others)
Exhaust Fan
Signal
External Output
Option 2 Device
(by Others)
Fault Indication
Shield
Note: Not all external input options are available for all models.
Figure 50: 12-pin plug MicroTech control wiring diagram
Note: Not all external input options are available for all models.
External Input
Option 3 Device
(by others)
Ventilation Lockout
(default) or
Exhaust Interlock
External Input
Option 2 Device
(by others)
Remote
Shutdown
External Input
Option 1 Device
(by others)
Unoccupied (default)
or Dewpoint Humidity
P1 (12-pin)
Connector
Unit Ventilator
P1 (12-pin)
Connector
Wall Sleeve
H6-8
H6-7
H6-6
H6-5
H6 4
H6-3
H6-1
H6-2
910
911
902
901
912
909
907
906
Remote Wall Sensor
(Option)
GND
UTS
FC
FM
SP
ST
OCC
24VAC
896
907
904
905
908
896
H6-1
H4-1
H4-2
H5-3
H5-4
24VAC
5
4
6
2
3
1
U
R
Shield
Shield
TB1 - 24VAC
Wire
Caps
TB1 - 24VAC
Not Used
Not Used