Control Specification
SiBE04-401
48
Function and Control
3.3.4
3-minutes Standby
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(Except when defrosting. (Only for Heat Pump Model).)
3.3.5
Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting (only for heat pump model).)
3.4
Discharge Pipe Control
Outline
The discharge pipe temperature is used as the compressor's internal temperature. If the
discharge pipe temperature rises above a certain level, the operating frequency upper limit is
set to keep this temperature from going up further.
Detail
Divide the Zone
Management within the Zones
FCG 3
FCG 2
FCG 1
TCG 1
TCG 2
TCG 3
88
64
48
240
360
180
Zone
Control contents
Stop zone
When the temperature reaches the stop zone, stop the compressor and
correct abnormality.
Drooping zone
Start the timer, and the frequency will be drooping.
Unchanged zone
Keep the upper limit of frequency.
Return / Reset zone
Cancel the upper limit of frequency.
Summary of Contents for ARKH20CVMB9
Page 67: ...Control Specification SiBE04 401 58 Function and Control ...
Page 97: ...Instruction SiBE04 401 88 System Configuration ...
Page 141: ...Check SiBE04 401 132 Service Diagnosis ...
Page 211: ...Outdoor Unit RK X H C ARK X H C R Y N C SiBE04 401 202 Removal Procedure ...
Page 215: ...Others SiBE04 401 206 Others ...