11
|
Configuration
Installer reference guide
168
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
#
Code
Description
[3.A]
[C‑06]
External room thermostat type for the additional
zone:
▪
1:
1 contact
. Connected to only 1 digital
input (X2M/35a)
▪
2:
2 contacts
. Connected to 2 digital inputs
(X2M/34a and X2M/35a)
Leaving water temperature: Delta T
#
Code
Description
[3.B.1]
[1-0C]
Delta T heating
: A minimum temperature
difference is required for the good operation of
heat emitters in heating mode.
▪
If [2-0D] = 2, this is fixed to 8°C
▪
Else: 3°C~10°C
[3.B.2]
[1-0E]
Delta T cooling
: A minimum temperature
difference is required for the good operation of
heat emitters in cooling mode.
▪
3°C~10°C
11.6.5 Space heating/cooling
Overview
The following items are listed in the submenu:
4
Space heating/cooling
Tank
Additional zone
Main zone
User settings
[4]
Space heating/cooling
[4.1]
Operation mode
[4.2]
Operation mode schedule
[4.3]
Operation range
[4.4]
Number of zones
[4.5]
Pump operation mode
[4.6]
Unit type
[4.7]
Pump limitation
[4.9]
Pump outside range
[4.A]
Increase around 0°C
[4.B]
Overshoot
[4.C]
Antifrost
About space operation modes
Your unit can be a heating or a heating/cooling model:
▪
If your unit is a heating model, it can heat up a space.
▪
If your unit is a heating/cooling model, it can both heat up and cool down a
space. You have to tell the system which operation mode to use.