9
|
Electrical installation
Installer reference guide
115
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
A4P.Y2
X2M.7
YC Y2
9
7
X1M
Y2
X2M
A4P
a
YC
a
Installation of EKRP1HBAA is required.
WARNING
Stripped wire.
Make sure that stripped wire cannot make contact with possible
water on the bottom plate.
3
Fix the cable with cable ties to the cable tie mountings.
9.2.11 To connect the changeover to external heat source
Wires: 2×0.75 mm²
Maximum load: 0.3 A, 250 V AC
Minimum load: 20 mA, 5 V DC
[9.C]
Bivalent
1
Open the service cover. See
72].
2
Connect the changeover to external heat source cable to the appropriate
terminals as shown in the illustration below.
A4P.X1
A4P.X2
N
L