7 Installation
Installer reference guide
41
EBLQ+EDLQ011~W1 + EK(2)CB
EKMB9W1
Daikin Altherma low temperature monobloc
4P522034-1 – 2018.01
Item
Tightening torque (N•m)
X4M
1.3~1.6
X8M
0.8~0.9
Backup heater
X15M
0.8~0.9
7.8.4
To connect the electrical wiring on the
outdoor unit
1
Remove the switch box cover. See
.
2
Strip insulation (20 mm) from the wires.
a
b
a
Strip wire end to this point
b
Excessive strip length may cause electrical shock or
leakage.
3
Insert the wiring from the back of the unit:
a
b
c
≥25 mm
a
Low voltage cable
b
High voltage cable
c
Power supply cable
NOTICE
The distance between the high voltage and low voltage
cables should be at least 25 mm.
Routing
Possible cables (depends on the installed
options)
a
Low voltage
▪ User interface
▪ Interconnection cable to control box
EKCB07CAV3
▪ Remote outdoor sensor (option)
b
High voltage
▪ Normal kWh rate power supply
▪ Preferential kWh rate power supply
▪ Heat pump convector (option)
▪ Shut-off valve (field supply)
▪ Domestic hot water pump (field supply)
▪ Space heat/cool operation control
c
Main power supply
▪ Main power supply
4
Inside the unit, route the wiring as follows:
b
a
V3
b
a
W1
a
Power supply cable
b
Cable tie
5
Make sure that the cable does NOT come in contact with sharp
edges.
6
Install the switch box cover.
INFORMATION
When installing field supply or option cables, foresee
sufficient cable length. This will make it possible to remove/
reposition the switch box and gain access to other
components during service.
CAUTION
Do NOT push or place redundant cable length in the unit.