External Backup Heater Kit
ESIE09-08A
262
Appendix
6.4
Detailed Explanation of Setting Modes
To activate the heater kit some field settings on the indoor unit need to be changed. For details how to
change field settings refer to the chapter "Field settings" of the indoor unit installation or operation
manual.
Detailed
description
[6-02] Heater kit
Once installed, you can activate the heater kit by changing field setting [6-02]=1. From that moment
on, the heat pump system will take the heater kit into account whilst deciding operation. When the
heater is actually operating, the heater symbol
(
is shown on the remote controller. There is no step
1-2 indication.
Use of backup heater with EKHBRD*AA*
(*) Auxilary relay (following heat pump tariff signal) can be applied to switch off BUH during HP
tariff operation
Use of backup heater with EKHBRD*AB*/EKHVMY(R)D*AA*
(*) Auxilary relay (following heat pump tariff signal) can be applied to switch off BUH during HP
tariff operation
Note
Setting [8-01]:
Not for EKHBRD*AA*: was used to set auto restart on or off. This has been changed to default on.
[8-02] Emergency operation
During emergency mode, heating is only done by the heater kit, not by the heat pump. Activation of
emergency mode is done by changing field setting [8-02]=1. Activating the emergency mode will
stop the heat pump operation. The pump of the indoor unit will be started, but heating itself is done by
the heater kit. If there are no error conditions in leaving or returning water thermistors, the heater kit
can start to follow emergency operation.
Note
Before activating emergency operation, be sure to activate the heater kit. The heater will stay in
emergency mode until the field setting is set back to default [8-02]=0.
Benefit kWh rate power supply mode
Note
This concerns the benefit kWh rate power supply mode of the EKHBRD/EKHVM indoor unit. For
more details, refer to the "Field settings" chapter of the indoor unit installation manual.
If the benefit kWh rate power supply is used for the indoor unit, the indoor unit will go into
emergency operation automatically when the power supply is interrupted.
[6-02]=0
[6-02]=1
Normal heat pump operation
BUH assistance possible
NO
YES
During heat pump tariff
BUH operation
NO
YES
(*)
Heat pump operation
NO
NO
Ta < -25°C
Automatic switch over to BUH
operation
NO
NO
[6-02]=0
[6-02]=1
[8-01]=0
[8-01]=1
[8-01]=0
[8-01]=1
Normal heat pump
operation
BUH assistance possible
NO
NO
YES
YES
During heat pump
tariff
BUH operation
NO
NO
NO
YES
Heat pump operation
NO
NO
NO
NO
Ta < -25°C
Automatic switch over
to BUH operation
NO
NO
NO
YES
(*)
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...