Troubleshooting by Indication on the Remote Controller
ESIE09-08A
220
Troubleshooting
[CHECK 2] Check for causes of drop in low pressure
Referring to the Fault Tree Analysis (FTA) shown below, probe the faulty points.
Abnormally low
low-pressure
(Low evaporating
temperature)
[Heating]
(See *1.)
Faulty outdoor
unit electronic
expansion valve
Faulty valve coil
Faulty valve body
←Are the coil resistance and insulation normal?
[In heating]
If the outdoor unit
electronic
expansion valve
excessively
throttled:
(See *2.)
Faulty
control
Faulty low pressure sensor
Faulty suction pipe thermistor
Faulty control PCB
←Are the electrical characteristics normal?
←Check for the thermistor resistance and
connection.
Low suction air
temperature of
the evaporator
[In heating]
Low suction air temperature of outdoor unit
←Is the outdoor temperature not less than -15°C
Faulty outdoor temperature thermistor of outdoor unit
←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
High pipe
resistance
Abnormal piping length
Bent or crashed pipe
Clogging of foreign particles
Stop valve closed
←Does the piping length fall in the permissible range?
←Conduct visual checks for pipe conditions.
←Is there any temperature difference caused before and
after the filter or branch pipe?
¬Check to be sure the stop valve is open.
Less
circulation
quantity of
refrigerant
Degradation in
condensing
capacity
Inadequate refrigerant quantity
←Refer to P.189.
Moisture choke
←Eliminate moisture by vacuum operation.
Dirty
evaporator
Decreased
fan airflow
rate
Decreased
fan output
Faulty fan motor
←Can the fan motor be rotated with hands?
Are the motor coil resistance and insulation normal?
←Is the heat exchanger clogged?
Faulty control PC board
(Including capacity setting)
←If a spare PC board is mounted, is the capacity
setting properly made?
High air
passage
resistance
Dirty filter
←Is there any obstacle in the air passage?
←Is the air filter clogged?
Obstacle
*1: The “low pressure protection control” includes low pressure protection control and hot gas bypass control. For details, refer to P.61.
*2: In heating, the outdoor unit electronic expansion valve (EV1) is used for “superheated degree control of outdoor unit heat exchanger”.
(For details, refer to P.51.)
Faulty electronic
expansion valve
control
C: SDK04009
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...