10
|
Commissioning
Installer reference guide
187
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
Air purge prerequisites
3
Install air purges on each part of the installation where the pipe work goes
down. (For example on a tank with connections on top.)
4
Fill the circuit to ±2 bar.
5
Purge all radiators and all other air purges installed on the circuit.
6
Repeat steps 2 and 3 until purging the radiators and the other points does NOT
longer lead to a pressure drop.
7
Make sure that the leaving water temperature home page, room temperature
home page, and domestic hot water home page are turned OFF.
When an air bubble blocks the pump and there is no flow, a 7H error can occur. In
this case, stop the air purge function and restart the operation. This will cause the
bubble to leave the pump. Make sure the pressure in the circuit is ±2 bar and refill
if necessary.
To check if the air purge function is finished, monitor the flow rate. If it stays
constant when the pump is running at high or low speed, the unit is properly
purged. To monitor the flow rate, go to [6.1.8].
The air purge function automatically stops after 42 minutes.
INFORMATION
For best results, air purge each loop separately.
To perform a manual air purge
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
2
Set the air purge mode: go to [A.7.3.1]
>
Installer settings
>
Commissioning
>
Air purge
>
Type
.
3
Select
Manual
and press .
4
Go to [A.7.3.4]
>
Installer settings
>
Commissioning
>
Air
purge
>
Start air purge
and press to start the air purge function.
Result:
The manual air purge starts and the following screen appears.
01:18
Tue
Air purge
l/min
Low
SHC
Yes
0.5
Flow rate
Speed
Circuit
Bypass
Stop
Adjust
Scroll
5
Use the and buttons to scroll to
Speed
.
6
Use the and buttons to set the desired pump speed.
Result:
Low
Result:
High
7
If applicable, set the desired position of the 3-way valve (space heating/
domestic hot water). Use the and buttons to scroll to
Circuit
.
8
Use the and buttons to set the desired position of the 3-way valve.
Result:
SHC
or
Tank
9
Set the desired position of the bypass valve. Use the and buttons to scroll to
Bypass
.