9
|
Electrical installation
Installer reference guide
132
ERGA04~08EA + EHBH/X04+08EF
Daikin Altherma 3 R W
4P629085-1B – 2021.11
B
C
A
A
14
Q4L
13
C
B
14
13
X5M
X5M
3
Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat according to the applicable
legislation.
In any case, to prevent unnecessary tripping of the safety thermostat, we
recommend the following:
▪
The safety thermostat is automatically resettable.
▪
The safety thermostat has a maximum temperature variation rate of 2°C/min.
▪
There is a minimum distance of 2 m between the safety thermostat and the
motorized 3‑way valve delivered with the domestic hot water tank.
NOTICE
Error.
If you remove the jumper (open circuit) but do NOT connect the safety
thermostat, stop error 8H-03 will occur.
9.3.11 To connect a Smart Grid
This topic describes 2 possible ways to connect the indoor unit to a Smart Grid:
▪
In case of low voltage Smart Grid contacts
▪
In case of high voltage Smart Grid contacts. This requires the installation of the
Smart Grid relay kit (EKRELSG).
The 2 incoming Smart Grid contacts can activate the following Smart Grid modes:
Summary of Contents for Altherma 3 R W
Page 292: ...11 11 ...
Page 293: ......
Page 294: ......
Page 295: ......
Page 296: ...4P629085 1B 2021 11 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...