Unit installation
Installer reference guide
74
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
PATTERN 3
No
Yes
START PATTERN 3
A
You can install the unit in room A if you lead the chimney outside
the building.
3a
You CANNOT install the unit in the room. Place the unit in a larger
room.
3b
See table 3:
Is it possible to lead a chimney
outside the building respecting the maximum
chimney length?
Tables for PATTERN 1, 2 and 3
Table 1: Minimum floor area
For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is
4.3 kg, use the row of 4.5 kg.
Minimum floor area (m²)
Charge (kg)
Release height without chimney (m)
1.66 (Unit=180 l)
1.86 (Unit=230 l)
3.8
16.04
12.76
4
17.77
14.14
4.5
22.49
17.90
5
27.76
22.09
5.5
33.59
26.73
5.8
37.36
29.73
Table 2: Minimum release height
Take the following into account:
•
For intermediate floor areas, use the column with the lower value.
Example:
If the floor area is 22.50 m², use the
column of 20.00 m².
•
For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is
4.3 kg, use the row of 4.5 kg.
•
(*): The release height of the unit without chimney (for 180 l units: 1.66 m; for 230 l units: 1.86 m) is already
higher than the minimum required release height. => OK (no chimney needed).
Minimum release height (m)
Charge (kg)
Floor area (m²)
5.00
10.00
15.00
20.00
25.00
30.00
35.00
3.8
3.30
2.10
1.72
(*)
(*)
(*)
(*)
4
3.47
2.21
1.81
(*)
(*)
(*)
(*)
4.5
3.91
2.49
2.03
1.76
(*)
(*)
(*)
5
4.34
2.77
2.26
1.96
1.75
(*)
(*)
5.5
4.78
3.04
2.49
2.15
1.93
1.76
(*)
5.8
5.04
3.21
2.62
2.27
2.03
1.85
1.72