14
|
Maintenance and service
Installer reference guide
262
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
4
Install the cleaned rolled‑up filter and strainer in the water filter housing.
INFORMATION
Correctly install the strainer in the magnetic filter/dirt separator housing using the
protrusions.
a
b
c
c
a
Rolled‑up filter
b
Strainer
c
Protrusion
5
Install and properly tighten the bottom of the water filter housing.
14.5.3 To install the water filter
NOTICE
Check the condition of the O-rings and replace if needed. Apply water to the O-rings
before installation.
1
Install the water filter in the correct location.
a
c
b
a
a
Clip
b
Magnetic filter/dirt separator
c
Air purge valve
2
Install the 2 clips to fix the water filter to the water circuit pipes.
3
Make sure that the air purge valve of the water filter is in the open position.
4
Open the stop valves and add water to the water circuit if needed.