10
|
Configuration
Installer reference guide
165
ERGA04~08EAV3(A) + 08S18+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
t
T
DHW
T
HP ON
T
HP OFF
T
HP MAX
T
U
=
T
BUH OFF
[6-01]
[6-00]
T
U
= 60°C
T
HP MAX
= 50°C
[6-01] = 2°C
[6-00] = 2°C
HP
BUH
HP
5
10
20
30
40
46
48
50
60
BUH
Backup heater
HP
Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by
the backup heater can take place
T
BUH OFF
Backup heater OFF temperature (T
U
)
T
HP MAX
Maximum heat pump temperature at sensor in domestic hot water tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature (as set on the user interface)
t
Time
Example: setpoint (T
U
)≤maximum heat pump temperature–[6‑01] (T
HP MAX
–[6‑01])
t
[6-00]
HP
5
10
20
30
40
43
45
T
U
=T
HP OFF
T
HP MAX
T
DHW
T
HP ON
50
HP
Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by
the backup heater can take place
T
HP MAX
Maximum heat pump temperature at sensor in domestic hot water tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature (as set on the user interface)
t
Time
INFORMATION
The maximum heat pump temperature depends on the ambient temperature. For
more information, see the operation range.
10.5.7 User settings
Overview
The following items are listed in the submenu: