Daikin Altherma 3 H W Installation Manual Download Page 9

4 Installation

Installation manual

9

EABH/9W
Daikin Altherma 3 H W
4P644479-1 – 2020.12

If…

Then…

The system does NOT contain a
domestic hot water tank

You can use either propylene
glycol

(a)

 or ethylene glycol

(a)

Propylene glycol, including the necessary inhibitors, classified as
Category III according to EN1717.

Required concentration of glycol

The  required  concentration  of  glycol  depends  on  the  lowest
expected  outdoor  temperature,  and  on  whether  you  want  to  protect
the  system  from  bursting  or  from  freezing.  To  prevent  the  system
from freezing, more glycol is required.

Add glycol according to the table below.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

–30°C

35%

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

NOTICE

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

Glycol and the maximum allowed water volume

Adding  glycol  to  the  water  circuit  reduces  the  maximum  allowed
water volume of the system. For more information, see the installer
reference guide (topic "To check the water volume and flow rate").

Glycol setting

NOTICE

If  glycol  is  present  in  the  system,  setting  [E-0D]  must  be
set to 1. If the glycol setting is NOT set correctly, the liquid
inside the piping can freeze.

Freeze protection by freeze protection valves

About freeze protection valves

When no glycol is added to the water, you can use freeze protection
valves to drain the water from the system before it can freeze.

▪ Install freeze protection valves (field supply) at all lowest points of

the field piping.

▪ Normally closed valves (located indoors near the piping entry/exit

points)  can  prevent  that  all  water  from  indoor  piping  is  drained
when the freeze protection valves open.

NOTICE

When  freeze  protection  valves  are  installed,  set  the
minimum cooling setpoint (default=8°C) at least 2°C higher
than  the  maximum  opening  temperature  of  the  freeze
protection  valve.  If  lower,  freeze  protection  valves  can
open during cooling operation.

For more information, see the installer reference guide.

Heater tape (field supply)

1

Install heater tape to the outdoor field piping.

2

Provide external power supply for the heater tape.

NOTICE

▪ For the internal heater tape to operate, the power to the

unit MUST be ON. For this reason, during cold periods,
never  disconnect  the  power,  nor  turn  off  the  main
switch.

▪ In  case  of  a  power  failure,  power  to  the  heater  tape

(both  internal  and  external)  will  be  aborted  and  the
water circuit will NOT be protected. To guarantee a full
protection,  it  is  always  possible  to  add  glycol  to  the
water  circuit  or  to  use  freeze  protection  valves,  even
when installing heater tape to the outdoor field piping.

4.3.4

To fill the domestic hot water tank

See the installation manual of the domestic hot water tank.

4.3.5

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

Outdoor water piping insulation

See  the  installation  manual  of  the  outdoor  unit,  or  the  installer
reference guide.

4.4

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

4.4.1

About electrical compliance

Only for the backup heater of the indoor unit

See 

"To connect the backup heater power supply"

 [

4

 11].

4.4.2

To connect the electrical wiring to the
indoor unit

1

Open  the  switch  box  so  that  you  can  access  the  back  of  the
switch box. See 

"To open the indoor unit"

 [

4

 6].

2

Route the wiring as follows:

▪ Enter the unit from the bottom.
▪ Route the wiring via the back of the switch box.
▪ Fix  the  cables  with  cable  ties  to  the  cable  tie  mountings  at

the back of the switch box.

Summary of Contents for Altherma 3 H W

Page 1: ...Installation manual Daikin Altherma 3 H W English Installation manual Daikin Altherma 3 H W EABH16DF6V EABH16DF9W EABX16DF6V EABX16DF9W...

Page 2: ...y odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 19...

Page 3: ...pendent curve 18 5 2 8 Configuration wizard Tank 19 5 3 Settings menu 19 5 3 1 Main zone 19 5 3 2 Additional zone 19 5 3 3 Information 20 5 4 Menu structure Overview installer settings 21 6 Commission...

Page 4: ...5 35 C Domestic hot water production 5 35 C INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHBCONV Mind the measurement guidelines Maximum hei...

Page 5: ...above the heat exchanger coil The booster heater must be located above the heat exchanger coil NOTICE Performance Performance data for third party tanks CANNOT be provided and performance CANNOT be g...

Page 6: ...Overview 1 2 3 1 4 4 1 Front panel 2 Switch box cover 3 Switch box 4 User interface panel Open 1 Remove the front panel 2 2 1 3 2 If you have to connect electrical wiring remove the switch box cover...

Page 7: ...he drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable legislation 1 Co...

Page 8: ...circuit against freezing Add glycol to the water Glycol lowers the freezing point of the water Install freeze protection valves Freeze protection valves drain the water from the system before it can...

Page 9: ...se freeze protection valves to drain the water from the system before it can freeze Install freeze protection valves field supply at all lowest points of the field piping Normally closed valves locate...

Page 10: ...y factory mounted cable Power supply for backup heater CAUTION Do NOT push or place redundant cable length in the unit 4 4 3 To connect the main power supply 1 Connect the main power supply In case of...

Page 11: ...er phase c This equipment complies with EN IEC 61000 3 11 European International Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply...

Page 12: ...ck the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Connect the electricity meters cable to the appropriate terminals as shown in the...

Page 13: ...tat normally closed cable to the appropriate terminals as shown in the illustration below X5M 9 10 2 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the...

Page 14: ...be displayed Accessing settings Legend for tables You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding ta...

Page 15: ...st be set on the user interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting...

Page 16: ...nd the zone with the highest water temperature is configured as the additional zone NOTICE If there are 2 zones and the emitter types are wrongly configured water of high temperature can be sent towar...

Page 17: ...T in heating 0 Underfloor heating Maximum 55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 65 C Fixed 8 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 T...

Page 18: ...n 3 1 N A 0 No 1 Yes 5 2 7 Detailed screen with weather dependent curve When weather dependent WD operation is active the desired leaving water or tank temperature is determined automatically dependin...

Page 19: ...t up until the storage comfort temperature has been reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature p...

Page 20: ...44479 1 2020 12 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 5 3 3 Information Dealer information The installer can fill in his contact numb...

Page 21: ...librium temperature Operation 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running t...

Page 22: ...tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification labe...

Page 23: ...evel 414 2 Go to A 2 Commissioning Actuator test run 3 Select a test from the list Example Pump 4 Select OK to confirm Result The actuator test run starts It stops automatically when ready 30 min To s...

Page 24: ...in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete doc...

Page 25: ...diagram Indoor unit 3D120613A R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut...

Page 26: ...t pump convector Safety thermostat Safety thermostat Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless...

Page 27: ...ater pump output DHW pump Domestic hot water pump Electrical meters Electricity meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load English Translation Norma...

Page 28: ...thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation 2 core 2 core communication 2x0 75...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...4P644479 1 2020 12 Copyright 2018 Daikin 4P644479 1 0000000W Verantwortung f r Energie und Umwelt...

Reviews: