Daikin Altherma 3 H W Installation Manual Download Page 5

3 Preparation

Installation manual

5

EABH/9W
Daikin Altherma 3 H W
4P644479-1 – 2020.12

3.2.1

To check the water volume and flow rate

Minimum water volume

Check  that  the  total  water  volume  in  the  installation  is  minimum  20
litres, the internal water volume of the outdoor unit NOT included.

NOTICE

When  circulation  in  each  space  heating/cooling  loop  is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves are closed.

Minimum flow rate

Check that the minimum flow rate in the installation is guaranteed in
all  conditions.  This  minimum  flow  rate  is  required  during  defrost/
backup  heater  operation.  For  this  purpose,  use  the  overpressure
bypass valve delivered with the unit, and respect the minimum water
volume.

Minimum required flow rate

20 l/min

NOTICE

To guarantee proper operation it is recommended to have
a minimum flow of 28 l/min during DHW.

NOTICE

If  glycol  was  added  to  the  water  circuit,  and  the
temperature  of  the  water  circuit  is  low,  the  flow  rate  will
NOT  be  displayed  on  the  user  interface.  In  this  case,  the
minimum  flow  rate  can  be  checked  by  way  of  the  pump
test (check that the user interface does NOT display error
7H).

NOTICE

When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating or operation).

See the installer reference guide for more information.

See  the  recommended  procedure  as  described  in 

"6.2  Checklist

during commissioning"

 [

4

 22].

3.2.2

Third-party tank requirements

In  case  of  a  third-party  tank,  the  tank  shall  adhere  to  the  following
requirements:

▪ The heat exchanger coil of the tank is ≥1.05 m².

▪ The  tank  thermistor  must  be  located  above  the  heat  exchanger

coil.

▪ The  booster  heater  must  be  located  above  the  heat  exchanger

coil.

NOTICE

Performance.

  Performance  data  for  third-party  tanks

CANNOT  be  provided,  and  performance  CANNOT  be
guaranteed.

NOTICE

Configuration.

 Configuration of a third-party tank depends

on the size of the heat exchanger coil of the tank. For more
information, see the installer reference guide.

3.3

Preparing electrical wiring

3.3.1

Overview of electrical connections for
external and internal actuators

Item

Description

Wires

Maximum

running

current

Outdoor unit and indoor unit power supply

1

Power supply for
outdoor unit

2+GND

(a)

2

Power supply and
interconnection cable to
indoor unit

3

(g)

3

Power supply for
backup heater

See table below. —

4

Preferential kWh rate
power supply (voltage
free contact)

2

(e)

5

Normal kWh rate power
supply

2

6.3 A

Optional equipment

6

3‑way valve

3

100 mA

(b)

7

Power supply for
booster heater and
thermal protection
(from indoor unit)

4+GND

(c)

8

Power supply for
booster heater (to
indoor unit)

2+GND

13 A

9

Domestic hot water
tank thermistor

2

(d)

10

User interface used as
room thermostat

2

(f)

11

Room thermostat

3 or 4

100 mA

(b)

12

Outdoor ambient
temperature sensor

2

(b)

13

Indoor ambient
temperature sensor

2

(b)

14

Heat pump convector

2

100 mA

(b)

Field supplied components

15

Shut-off valve

2

100 mA

(b)

16

Electricity meter

2 (per meter)

(b)

17

Domestic hot water
pump

2

(b)

18

Alarm output

2

(b)

19

Changeover to external
heat source control

2

(b)

20

Space cool/heat
operation control

2

(b)

21

Power consumption
digital inputs

2 (per input
signal)

(b)

22

Safety thermostat

2

(e)

(a)

Refer to name plate on outdoor unit.

(b)

Minimum cable section 0.75 mm².

(c)

Cable section 2.5 mm².

(d)

The thermistor and connection wire (12 m) are delivered
with the domestic hot water tank.

(e)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
50 m. Voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.

(f)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
500 m. Applicable for both single user interface and dual
user interface connection.

(g)

Cable section 1.5 mm².

Summary of Contents for Altherma 3 H W

Page 1: ...Installation manual Daikin Altherma 3 H W English Installation manual Daikin Altherma 3 H W EABH16DF6V EABH16DF9W EABX16DF6V EABX16DF9W...

Page 2: ...y odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 19...

Page 3: ...pendent curve 18 5 2 8 Configuration wizard Tank 19 5 3 Settings menu 19 5 3 1 Main zone 19 5 3 2 Additional zone 19 5 3 3 Information 20 5 4 Menu structure Overview installer settings 21 6 Commission...

Page 4: ...5 35 C Domestic hot water production 5 35 C INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHBCONV Mind the measurement guidelines Maximum hei...

Page 5: ...above the heat exchanger coil The booster heater must be located above the heat exchanger coil NOTICE Performance Performance data for third party tanks CANNOT be provided and performance CANNOT be g...

Page 6: ...Overview 1 2 3 1 4 4 1 Front panel 2 Switch box cover 3 Switch box 4 User interface panel Open 1 Remove the front panel 2 2 1 3 2 If you have to connect electrical wiring remove the switch box cover...

Page 7: ...he drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable legislation 1 Co...

Page 8: ...circuit against freezing Add glycol to the water Glycol lowers the freezing point of the water Install freeze protection valves Freeze protection valves drain the water from the system before it can...

Page 9: ...se freeze protection valves to drain the water from the system before it can freeze Install freeze protection valves field supply at all lowest points of the field piping Normally closed valves locate...

Page 10: ...y factory mounted cable Power supply for backup heater CAUTION Do NOT push or place redundant cable length in the unit 4 4 3 To connect the main power supply 1 Connect the main power supply In case of...

Page 11: ...er phase c This equipment complies with EN IEC 61000 3 11 European International Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply...

Page 12: ...ck the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Connect the electricity meters cable to the appropriate terminals as shown in the...

Page 13: ...tat normally closed cable to the appropriate terminals as shown in the illustration below X5M 9 10 2 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the...

Page 14: ...be displayed Accessing settings Legend for tables You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding ta...

Page 15: ...st be set on the user interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting...

Page 16: ...nd the zone with the highest water temperature is configured as the additional zone NOTICE If there are 2 zones and the emitter types are wrongly configured water of high temperature can be sent towar...

Page 17: ...T in heating 0 Underfloor heating Maximum 55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 65 C Fixed 8 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 T...

Page 18: ...n 3 1 N A 0 No 1 Yes 5 2 7 Detailed screen with weather dependent curve When weather dependent WD operation is active the desired leaving water or tank temperature is determined automatically dependin...

Page 19: ...t up until the storage comfort temperature has been reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature p...

Page 20: ...44479 1 2020 12 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 5 3 3 Information Dealer information The installer can fill in his contact numb...

Page 21: ...librium temperature Operation 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running t...

Page 22: ...tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification labe...

Page 23: ...evel 414 2 Go to A 2 Commissioning Actuator test run 3 Select a test from the list Example Pump 4 Select OK to confirm Result The actuator test run starts It stops automatically when ready 30 min To s...

Page 24: ...in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete doc...

Page 25: ...diagram Indoor unit 3D120613A R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut...

Page 26: ...t pump convector Safety thermostat Safety thermostat Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless...

Page 27: ...ater pump output DHW pump Domestic hot water pump Electrical meters Electricity meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load English Translation Norma...

Page 28: ...thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation 2 core 2 core communication 2x0 75...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...4P644479 1 2020 12 Copyright 2018 Daikin 4P644479 1 0000000W Verantwortung f r Energie und Umwelt...

Reviews: