10
|
Configuration
Installer reference guide
219
EPRA08~W1 + ETBH/9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03
Bizone kit
Bizone kit installed
#
Code
Description
[9.P.1]
[E-0B]
Bizone kit installed
:
▪
0
No
: The system only has a main zone.
▪
1 N/A
▪
2
Yes
: A bizone kit is installed in order to add
an additional temperature zone.
Bizone kit system type
#
Code
Description
[9.P.2]
[E-0C]
Bizone system type
▪
0
Without hydraulic separator / no
direct pump
b
a
▪
1
With hydraulic separator / no
direct pump
b
a
c
▪
2
With hydraulic separator / with
direct pump
d
c
b
a
a
: Indoor unit;
b
: Mixing station;
c
: Hydraulic
separator;
d
: Direct pump
Additional zone pump fixed PWM
The speed of the additional zone pump can be fixed with this setting.
Summary of Contents for Altherma 3 H MT W