10
|
Configuration
Installer reference guide
132
EPRA08~W1 + ET9W
Daikin Altherma 3 H MT F
4P634887-1 – 2021.03
Types of weather-dependent curve
There are 2 types of weather-dependent curves:
▪
2-points curve
▪
Slope-offset curve
Which type of curve you use to make adjustments, depends on your personal
preference. See
"10.4.4 Using weather-dependent curves"
Availability
The weather-dependent curve is available for:
▪
Main zone - Heating
▪
Main zone - Cooling
▪
Additional zone - Heating
▪
Additional zone - Cooling
▪
Tank (only available to installers)
INFORMATION
To operate weather dependent, correctly configure the setpoint of the main zone,
additional zone or tank. See
"10.4.4 Using weather-dependent curves"
134].
10.4.2 2-points curve
Define the weather-dependent curve with these two setpoints:
▪
Setpoint (X1, Y2)
▪
Setpoint (X2, Y1)
Example
Y1
Y2
X1
X2
a