6 Electrical installation
Installation manual
16
ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH
₂
O
4P679468-1B – 2022.09
6
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length into the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
6.1
About electrical compliance
Only for the backup heater of the indoor unit
See
"6.3.3 To connect the backup heater power supply"
19].
6.2
Guidelines when connecting the
electrical wiring
Tightening torques
Indoor unit:
Item
Tightening torque (N•m)
M4 (X1M)
1.2
M4 (X12M, X15M)
0.88 ±10%
Indoor unit – BUH option:
Item
Tightening torque (N•m)
M4 (X6M) *3V, *6V
2.45 ±10%
M4 (X6M) *9W
1.2
6.3
Connections to the indoor unit
Item
Description
Power supply (main)
"6.3.2 To connect the main power
Power supply (backup
heater)
"6.3.3 To connect the backup heater
Backup heater
"6.3.4 To connect the backup heater to
Shut-off valve
"6.3.5 To connect the shut-off
Electricity meters
"6.3.6 To connect the electricity
Domestic hot water
pump
"6.3.7 To connect the domestic hot
Alarm output
22].
Space cooling/heating
operation control
"6.3.9 To connect the space cooling/
Changeover to
external heat source
control
"6.3.10 To connect the changeover to
Power consumption
digital inputs
Safety thermostat
thermostat (normally closed
contact)"
Smart Grid
Item
Description
WLAN cartridge
See
cartridge (delivered as accessory)"
Solar input
See
DHW output
See
Room thermostat
(wired or wireless)
See below table.
Wires: 0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Ext thermostat type
For the additional zone:
▪ [3.A]
Ext thermostat type
▪ [3.9] (read-only)
Control
Heat pump convector
There are different controllers and
setups possible for the heat pump
convectors.
Depending on the setup, you also
need option EKRELAY1.
For more information, see:
▪ Installation manual of the heat
pump convectors
▪ Installation manual of the heat
pump convector options
▪ Addendum
book
for
optional
equipment
Wires: 0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Ext thermostat type
For the additional zone:
▪ [3.A]
Ext thermostat type
▪ [3.9] (read-only)
Control
Remote outdoor
sensor
See:
▪ Installation manual of the remote
outdoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=1 (
External sensor
=
Outdoor
)
[9.B.2]
Ext. amb. sensor offset
[9.B.3]
Averaging time
Remote indoor sensor
See:
▪ Installation manual of the remote
indoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (
External sensor
=
Room
)
[1.7]
Room sensor offset