Electrical installation
Installer reference guide
112
EPRA14~W1 + ETBH/9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
C
B
5
6
3
4
X5M
X5M
3
Fix the cable with cable ties to the cable tie mountings.
8.3.5 To connect the domestic hot water pump
Wires: (2+GND)×0.75 mm²
DHW pump output. Maximum load: 2 A (inrush), 230 V AC, 1 A
(continuous)
[9.2.2]
DHW pump
[9.2.3]
DHW pump schedule
1
"6.2.5 To open the indoor unit"
65]):
1
Front panel
1
2
3
2
Switch box cover
3
Switch box
2
Connect the domestic hot water pump cable to the appropriate terminals as
shown in the illustration below.