Malfunctioning
Room
Operation
User profile
Main zone
10.5.2 Room
Setpoint screen
Control the room temperature of the main zone via setpoint screen [1]
Room
.
95].
Schedule
Indicate if the room temperature is controlled according to a schedule or not.
#
Code
Description
[1.1]
N/A
Schedule
:
▪
No
: Room temperature is directly controlled by
the user.
▪
Yes
: Room temperature is controlled by a
schedule and can be modified by the user.
Heating schedule
Applicable for all models.
Define a heating schedule of the room temperature in [1.2]
Heating schedule
.
"10.3.7 Schedule screen: Example"
Cooling schedule
Only applicable if EKHVCONV2 is installed.
Define a cooling schedule of the room temperature in [1.3]
Cooling schedule
.
"10.3.7 Schedule screen: Example"
Antifrost
Room frost protection [1.4] prevents the room from getting too cold. This setting
behaves differently depending on the set unit control method [2.9]. Perform
actions according to the table below.
Main zone unit control method [2.9]
Description
Leaving water temperature control
([C
‑
07]=0)
Room frost protection is NOT guaranteed.
External room thermostat control
([C
‑
07]=1)
Allow for the external room thermostat to
take care of room frost protection:
▪
Set
[C.2]
Space
heating/
cooling
=
On
.
Room thermostat control
([C
‑
07]=2)
Allow for the user interface used as room
thermostat to take care of room frost
protection:
▪
Set antifrost [1.4.1]
Activation
=
Yes
.
▪
Set the temperature of the antifrost
function in [1.4.2]
Room setpoint
.