6 Electrical installation

Installation manual

11

EA23DA6V(7)+9W
Daikin Altherma 3 H F
4P556073-1A – 2021.09

WARNING

ALWAYS use multicore cable for power supply cables.

6.1

About electrical compliance

Only for the backup heater of the indoor unit

See 

"6.3.4 To connect the backup heater power supply"

 [

4

 13].

6.2

Guidelines when connecting the
electrical wiring

Tightening torques

Indoor unit:

Item

Tightening torque (N•m)

X1M

2.45 ±10%

X2M

0.88 ±10%

X5M

0.88 ±10%

X6M

2.45 ±10%

X10M

0.88 ±10%

M4 (earth)

1.47 ±10%

6.3

Connections to the indoor unit

6.3.1

Overview of electrical connections for
external and internal actuators

Item

Description

Wires

Maximum

running

current

Outdoor unit and indoor unit power supply

1

Power supply for
outdoor unit

2+GND

(a)

2

Power supply and
interconnection cable to
indoor unit

3

(f)

3

Power supply for
backup heater

See table below. —

4

Preferential kWh rate
power supply (voltage
free contact)

2

(d)

5

Normal kWh rate power
supply

2

6.3 A

Optional equipment

6

User interface used as
room thermostat

2

(e)

7

Room thermostat

3 or 4

100 mA

(b)

8

Outdoor ambient
temperature sensor

2

(b)

9

Indoor ambient
temperature sensor

2

(b)

10

Heat pump convector

2

100 mA

(b)

Field supplied components

11

Shut-off valve

2

100 mA

(b)

12

Electricity meter

2 (per meter)

(b)

13

Domestic hot water
pump

2

(b)

14

Alarm output

2

(b)

15

Changeover to external
heat source control

2

(b)

Item

Description

Wires

Maximum

running

current

16

Space heating
operation control

2

(b)

17

Power consumption
digital inputs

2 (per input
signal)

(b)

18

Safety thermostat for
the main zone

2

(b)

19

Safety thermostat for
the additional zone

2

(d)

(a)

Refer to name plate on outdoor unit.

(b)

Minimum cable section 0.75 mm².

(c)

Cable section 2.5 mm².

(d)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
50 m. Voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.

(e)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
500 m.

(f)

Cable section 1.5 mm².

NOTICE

More  technical  specifications  of  the  different  connections
are indicated on the inside of the indoor unit.

Backup heater

type

Power supply

Required number of

conductors

*6V

1N~ 230 V (6V)

2+GND

3~ 230 V (6T1)

3+GND

*9W

3N~ 400 V

4+GND

6.3.2

To connect the electrical wiring to the
indoor unit

1

To  open  the  indoor  unit,  see 

"4.2.1  To  open  the  indoor

unit"

 [

4

 5].

2

The wiring enters the unit from the top:

b+c

a

d

a, b, c

Field wiring (see table below)

d

Factory-mounted cable for power supply of backup heater

3

Routing  of  the  wiring  inside  the  unit  should  be  as  follows.  Fix
the cable to the cable rail using cable ties:

a

b+c

Summary of Contents for Altherma 3 H F

Page 1: ...Installation manual Daikin Altherma 3 H F English Installation manual Daikin Altherma 3 H F EAVZ16S18DA6V 7 EAVZ16S23DA6V 7 EAVZ16S18DA9W EAVZ16S23DA9W...

Page 2: ...souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na i...

Page 3: ...ge 17 7 2 2 Configuration wizard Time and date 17 7 2 3 Configuration wizard System 17 7 2 4 Configuration wizard Backup heater 18 7 2 5 Configuration wizard Main zone 19 7 2 6 Configuration wizard Ad...

Page 4: ...iping installation 48 WARNING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 WARNING Ethylene glycol is toxic WARNING Due to the presence...

Page 5: ...heater 4 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Space heating operation 5 30 C Space...

Page 6: ...ng cases 4 2 2 To lower the switch box on the indoor unit 46 4 3 2 To connect the drain hose to the drain 47 When you need access to the high voltage switch box 2 T25 5 If you need access to the high...

Page 7: ...hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximum...

Page 8: ...ntrolled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or o...

Page 9: ...en All automatic air purge valves MUST remain open after commissioning 5 2 4 To protect the water circuit against freezing About freeze protection Frost can damage the system To prevent the hydraulic...

Page 10: ...e maximum allowed water volume Adding glycol to the water circuit reduces the maximum allowed water volume of the system For more information see the installer reference guide topic To check the water...

Page 11: ...mA b Field supplied components 11 Shut off valve 2 100 mA b 12 Electricity meter 2 per meter b 13 Domestic hot water pump 2 b 14 Alarm output 2 b 15 Changeover to external heat source control 2 b Item...

Page 12: ...ables 6 3 3 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M X2M X5M A5P X11YB X1A 1 2 3 1 2 3 a X11Y X11YA 1 2 3 a Interconnection cable ma...

Page 13: ...l Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedan...

Page 14: ...to the appropriate terminals as shown in the illustration below X1M X2M X5M 1 M M2P 1 2 2 Fix the cable with cable ties to the cable tie mountings 6 3 8 To connect the alarm output 1 Connect the alar...

Page 15: ...is too high the contact will open and the user interface will show a 8H 02 error ONLY the main pump will stop Additional zone 3 Connect the safety thermostat normally closed cable to the appropriate...

Page 16: ...access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable...

Page 17: ...r interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting determines if the sy...

Page 18: ...European electricity grids If the backup heater is available the voltage configuration and capacity must be set on the user interface The capacities for the different steps of the backup heater must...

Page 19: ...55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 65 C Fixed 8 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means that for a same leaving water te...

Page 20: ...the scheduled heat up cycles reheat operation is allowed 2 Schedule only The domestic hot water tank can ONLY be heated according to a schedule See the operation manual for more details Comfort setpoi...

Page 21: ...curves 422 7 3 2 2 points curve Define the weather dependent curve with these two setpoints Setpoint X1 Y2 Setpoint X2 Y1 Example Y1 Y2 X1 X2 a Item Description a Selected weather dependent zone Main...

Page 22: ...g Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather depende...

Page 23: ...at indoor unit b External room thermostat at main zone c External room thermostat at additional zone NOTICE If an external room thermostat is used the external room thermostat will control the room f...

Page 24: ...2 Capacity step 1 Equilibrium Equilibrium temperature Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running t...

Page 25: ...oltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the...

Page 26: ...correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go...

Page 27: ...result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user...

Page 28: ...rew connection 1 p Water filter main mixed zone b1 Space heating main mixed zone Water IN screw connection 1 q Loose nut 1 b2 Space heating main mixed zone Water OUT screw connection 1 B1L Flow sensor...

Page 29: ...n OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Positi...

Page 30: ...ad Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat Safety thermostat English Translation Safety thermostat contact 16 V DC detection voltage supplied by PCB...

Page 31: ...uded signal A13P P1 P2 LAN adapter A14P P1 P2 user interface communication 2 core communication 2 core 4 core 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H...

Page 32: ...4P556073 1A 2021 09 Copyright 2018 Daikin 4P556073 1 A 0000000 Verantwortung f r Energie und Umwelt...

Reviews: