background image

Installation manual

Daikin Altherma 3 H F

English

Installation manual

Daikin Altherma 3 H F

EAVH16SU18DA6V
EAVH16SU23DA6V

Summary of Contents for Altherma 3 H F EAVH16SU18DA6V

Page 1: ...Installation manual Daikin Altherma 3 H F English Installation manual Daikin Altherma 3 H F EAVH16SU18DA6V EAVH16SU23DA6V ...

Page 2: ...užívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następujących norm ...

Page 3: ...figuration wizard Language 16 5 2 2 Configuration wizard Time and date 16 5 2 3 Configuration wizard System 16 5 2 4 Configuration wizard Backup heater 17 5 2 5 Configuration wizard Main zone 18 5 2 6 Configuration wizard Additional zone 19 5 2 7 Detailed screen with weather dependent curve 19 5 2 8 Configuration wizard Tank 19 5 3 Settings menu 20 5 3 1 Main zone 20 5 3 2 Additional zone 20 5 3 3...

Page 4: ...o the Stand By Me platform is required to access the app App Store Google Play 2 About the box 2 1 Indoor unit INFORMATION This unit has been tested and approved according to BS EN12897 2016 2 1 1 To remove the accessories from the indoor unit 1 4 8 1 1 1 4 1 1 1 1 1 a b c d e j k l f g h i a Shut off valves for water circuit b Overpressure bypass valve c Tundish to mount onto the pressure relief ...

Page 5: ...m 100 INFORMATION If you have limited installation space do the following before installing the unit in its final position 4 2 2 To connect the drain hose to the drain 48 It requires to remove one or both side panels 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tight according to DIN 4726 The diffusion of oxygen into the piping can lead to ex...

Page 6: ...ntrol 2 b 16 Space cool heat operation control 2 b 17 Power consumption digital inputs 2 per input signal b 18 Safety thermostat 2 d a Refer to name plate on outdoor unit b Minimum cable section 0 75 mm c Cable section 2 5 mm d Cable section 0 75 mm till 1 25 mm maximum length 50 m Voltage free contact shall ensure the minimum applicable load of 15 V DC 10 mA e Cable section 0 75 mm till 1 25 mm m...

Page 7: ...t To have easier front access put the switch box lower on the unit as follows Prerequisite The user interface panel and front panel have been removed 1 Remove the fixing plate at the top of the unit 2 Tilt the switch box to the front and lift it out of its hinges 1 2 2 T25 3 Place the switch box lower on the unit Use the 2 hinges located lower on the unit 3 3 4 2 Mounting the indoor unit 4 2 1 To ...

Page 8: ...3 Connecting water piping 4 3 1 To connect the water piping NOTICE Do NOT use excessive force when connecting the field piping and make sure the piping is aligned properly Deformation of the piping can cause malfunctioning of the unit NOTICE Do NOT use excessive force when connecting the piping Deformation of the piping can cause malfunctioning of the unit 1 Connect the O rings and shut off valves...

Page 9: ...software is equipped with special frost protection functions such as water pipe freeze prevention and drain prevention see the installer reference guide that include the activation of pump in case of low temperatures However in case of a power failure these functions cannot guarantee protection Do one of the following to protect the water circuit against freezing Add glycol to the water Glycol low...

Page 10: ...ion see the installer reference guide topic To check the water volume and flow rate Glycol setting NOTICE If glycol is present in the system setting E 0D must be set to 1 If the glycol setting is NOT set correctly the liquid inside the piping can freeze Freeze protection by freeze protection valves About freeze protection valves When no glycol is added to the water you can use freeze protection va...

Page 11: ...consumption digital inputs field supply Outdoor ambient temperature sensor option Indoor ambient temperature sensor option Electrical meters field supply Safety thermostat field supply Routing Possible cables depending on unit type and installed options b High voltage power supply Interconnection cable Normal kWh rate power supply Preferential kWh rate power supply c High voltage control signal He...

Page 12: ...ding on the indoor unit model Make sure that the power supply is in accordance with the backup heater capacity as listed in the table below Backup heater type Backup heater capacity Power supply Maximum running current Zmax 6V 2 kW 1N 230 V a 9 A 4 kW 1N 230 V a 17 A b c 0 22 Ω 6 kW 1N 230 V a 26 A b c 0 22 Ω 2 kW 3 230 V d 5 A 4 kW 3 230 V d 10 A 6 kW 3 230 V d 15 A a 6V b Electrical equipment co...

Page 13: ...tration below NOTICE Wiring is different for a NC normally closed valve and a NO normally open valve X1M X2M X1M X2M NO NC M2S M2S 21 28 21 29 2 Fix the cable with cable ties to the cable tie mountings 4 4 6 To connect the electricity meters INFORMATION In case of an electricity meter with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative ...

Page 14: ...cable to the appropriate terminals as shown in the illustration below X1M X2M A8P X5M 1 2 3 4 5 X801M S6S S7S S8S S9S a a Installation of EKRP1AHTA is required 2 Fix the cable with cable ties to the cable tie mountings 4 4 12 To connect the safety thermostat normally closed contact 1 Connect the safety thermostat normally closed cable to the appropriate terminals as shown in the illustration below...

Page 15: ...onfiguration wizard go to Installer settings Configuration wizard To access Installer settings see 5 1 1 To access the most used commands 415 Afterwards If necessary you can make changes to the configuration in the menu structure or the overview settings INFORMATION When the configuration wizard is finished the user interface will show an overview screen and request to confirm When confirmed the s...

Page 16: ...cription 7 1 N A Language 5 2 2 Configuration wizard Time and date Code Description 7 2 N A Set the local time and date INFORMATION By default daylight savings time is enabled and clock format is set to 24 hours If you want to change these settings you can do this in the menu structure User settings Time date once the unit is initialised 5 2 3 Configuration wizard System Indoor unit type The indoo...

Page 17: ...ating To avoid this Install an aquastat thermostatic valve to avoid too high temperatures towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance with the connected emitter NOTICE An overpressure bypass valve can be integrated in the system Keep in mind that this valve might not be shown on the illustration...

Page 18: ...imum 65 C Fixed 8 C NOTICE For radiators the average emitter temperature will be lower compared to underfloor heating due to the fixed delta T of 8 C To compensate you can Increase the weather dependent curve desired temperatures 2 5 Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controlled Control In this control...

Page 19: ...th weather dependent curve When weather dependent WD operation is active the desired leaving water or tank temperature is determined automatically depending on the averaged outdoor temperature When the outdoor temperature is lower the leaving water or tank temperature will need to be higher as the water pipes will be colder and vice versa 2 points WD curve The weather dependent curve is defined by...

Page 20: ...low this value the tank is heated up during storage comfort to prioritize the domestic hot water preparation When the tank temperature rises above this value domestic hot water preparation and space heating cooling are executed sequentially Code Description 5 4 6 0C Reheat setpoint 30 C min 50 6 0E C 5 3 Settings menu You can set additional settings using the main menu screen and its submenus The ...

Page 21: ...Capacity step 1 Equilibrium Equilibrium temperature Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 8 Benefit kWh power supply Benefit kWh power supply Allow heater Allow pump 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Pri...

Page 22: ... installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON The correct ...

Page 23: ... the water circuit during the test run Shut off valve test Diverter valve test 3 way valve for switching between space heating and tank heating Bivalent signal test Alarm output test C H signal test DHW pump test 6 2 5 To perform an underfloor heating screed dryout Conditions Make sure all operation is disabled Go to C Operation and turn off Room Space heating cooling and Tank operation 1 Set the ...

Page 24: ...tying the dirt separator as follows 1 Take off the magnetic sleeve b 2 Unscrew the drain cap d 3 Connect a drain hose to the bottom of the water filter so that the water and dirt can be collected in a suitable container bottle sink 4 Open the drain valve for a couple of seconds c Result Water and dirt will come out 5 Close the drain valve 6 Screw the drain cap back on 7 Reattach the magnetic sleev...

Page 25: ...ot water tank is a stainless steel cylinder We recommend to use a non chloride based disinfectant approved for use with water intended for human consumption NOTICE When using means for descaling or chemical disinfection it must be ensured that the water quality remains compliant with EU directive 98 83 EC Pressure reducing valve Depending on local water conditions annual inspection of the integral...

Page 26: ...pen the indoor unit 6 8 7 About cleaning the water filter in case of trouble INFORMATION For yearly maintenance you do not have to remove the water filter from the unit to clean it But in case of trouble with the water filter you might have to remove it so that you can thoroughly clean it Then you need to do as follows 8 7 1 To remove the water filter 426 8 7 2 To clean the water filter in case of...

Page 27: ... magnetic filter dirt separator a b a Bottom part to be unscrewed b Water filter housing 3 Remove the strainer and the rolled up filter from the water filter housing and clean with water 4 Install the cleaned rolled up filter and strainer in the water filter housing INFORMATION Correctly install the strainer in the magnetic filter dirt separator housing using the protrusions a b c c a Rolled up fi...

Page 28: ...ndoor unit B Field installed a1 Space heating water IN a2 Space heating water OUT b1 Domestic hot water cold water IN loose nut 3 4 b2 Domestic hot water hot water OUT loose nut 3 4 c1 Water IN connection c2 Water OUT connection d Pump e Backup heater f Shut off valve male female 1 g Expansion vessel h Magnetic filter dirt separator i Safety valve j Air purge k Drain valve l Loose nut 1 B1L Flow s...

Page 29: ...OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P On OFF thermostat PC power circuit A3P Heat pump convector A4P Digital I O PCB A8P Demand PCB A10P MMI user interface connected to the indoor unit Power supply u...

Page 30: ...ormally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat contact 16 V DC detection voltage supplied by PCB English Translation Shut off valve Shut off valve SWB Switch box 7 Option PCBs 7 Option PCBs Alarm output Alarm output Changeover to ext heat source Changeover to external heat source Max load Maximum load Min load Minimum load Only for ...

Page 31: ...l 2 core 2 core 2 core signal 2 core 2 core External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only for BRC1HH Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2 core communication ...

Page 32: ...6486 1 2019 12 9 3 Technical specifications Domestic hot water tank 9 3 1 Test results in accordance with EN12897 2016 Description Test result Hot water capacity 160 l Reheat time 14 min INFORMATION This unit has been tested and approved according to BS EN12897 2016 9 3 2 Warning label ...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...4P606486 1 2019 12 Copyright 2019 Daikin 4P606486 1 0000000S Verantwortung für Energie und Umwelt ...

Reviews: