4 Operation

User reference guide

16

EGSAH/X06+10DA9W(G)

Daikin Altherma 3 GEO

4P569819-1 – 2019.02

4.6

Space heating/cooling control

4.6.1

About space heating/cooling control

Controlling  space  heating/cooling  typically  consists  of  the  following
stages:

1

Setting the space operation mode

2

Controlling the temperature

Depending on the system layout and installer configuration, you use
a different temperature control:

▪ Room thermostat control

▪ Leaving water temperature control

▪ External room thermostat control

4.6.2

Setting the space operation mode

About space operation modes

Depending  on  your  heat  pump  model,  you  have  to  tell  the  system
which space operation mode to use: heating or cooling.

If a … heat pump

model is installed

Then…

Heating/cooling

The system can heat up and cool down a
space. You have to tell the system which
space operation mode to use.

Heating only

The system can heat up a space, but
NOT cool down a space. You do NOT
have to tell the system which space
operation mode to use.

To determine if a heating/cooling heat pump model is installed

1

Go to [4]: 

Space heating/cooling

.

2

Check if [4.1] 

Operation mode

 is listed and editable.

If so, a heating/cooling heat pump model is installed.

To tell the system which space operation to use, you can:

You can…

Location

Check

 which space operation mode is

currently used

.

Home screen

Set

 the space operation 

mode 

permanently. Main menu

Restrict

 

automatic changeover

 according

to a monthly schedule.

To check which space operation mode is currently used

The space operation mode is displayed on the home screen:

▪ When the unit is in heating mode, the 

 icon is shown.

▪ When the unit is in cooling mode, the 

 icon is shown.

The status indicator shows if the unit is currently in operation:

▪ When the unit is not in operation, the status indicator will show a

blue pulsation with an interval of approximately 5 seconds.

▪ While the unit is in operation, the status indicator will light up blue

constantly.

To set the space operation mode

1

Go to [4.1]: 

Space heating/cooling

 > 

Operation

mode

2

Select one of the following options:

Heating

: Only heating mode

Cooling

: Only cooling mode

Automatic

The 

operation 

mode 

changes

automatically  based  on  the  outdoor  temperature.
Restricted  according  to  the  operation  mode
schedule.

Automatic  heating/cooling  changeover  is  is  NOT  applicable  for
heating only models. When 

Automatic

 is selected, the changing of

the  operation  mode  is  based  on  the 

Operation  mode  schedule

[4.2].

To restrict automatic changeover according to a schedule

Conditions: 

You set the space operation mode to 

Automatic

.

1

Go to [4.2]: 

Space heating/cooling

 > 

Operation

mode schedule

.

2

Select a month.

3

For each month, select an option:

Reversible

: Not restricted

Heating only

: Restricted

Cooling only

: Restricted

4

Confirm the changes.

Example: Changeover restrictions

When

Restriction

During cold season.

Example: 

October, November,

December, January, February and March.

Heating only

During warm season.

Example: 

June, July and August.

Cooling only

In-between.

Example: 

April, May and September.

Heating/Cooling

If  both  the 

Operation  mode

  and  the 

Operation  mode  schedule

are set to 

Automatic

, the operation mode will be determined by the

outdoor temperature.

4.6.3

Determining which temperature control
you are using

To determine which temperature control you are
using (method 1)

Check the installer settings table filled in by the installer.

To determine which temperature control you are
using (method 2)

You can see on the home screen which temperature control you are
using.

6

1.6

bar

26 Feb 2019

22:19

55

21
45

18

a2

a1

b

a1

Heat emitter of the main zone (in this example 

Underfloor

heating

)

a2

Heat emitter of the additional zone (in this example

Radiator

). If no icon is displayed, there is no additional

zone.

b

Room thermostat type of the main zone:

Summary of Contents for Altherma 3 GEO

Page 1: ...User reference guide Daikin Altherma 3 GEO English User reference guide Daikin Altherma 3 GEO EGSAH06DA9W EGSAH10DA9W EGSAX06DA9W G EGSAX10DA9W G...

Page 2: ...DHW powerful operation 19 4 8 Preset values and schedules 20 4 8 1 Using preset values 20 4 8 2 Setting the energy prices 20 4 8 3 Using and programming schedules 21 4 8 4 Schedule screen Example 21 4...

Page 3: ...al menu items for the user are now visible 1234 Advanced user 2 2 Space heating cooling To turn room temperature control ON or OFF 1 Go to C 1 Operation Room Operation Room Space heating cooling On On...

Page 4: ...the new preferred temperature at X1 is unequally higher than the preferred temperature at X2 X1 X2 c d Y1 Y2 Y3 Y4 a b Offset When offset is changed the new preferred temperature at X1 is equally high...

Page 5: ...type in 2 E Main zone WD curve type The way to adjust the curve depends on the type Slope offset curve Slope When slope is changed the new preferred temperature at X1 is unequally higher than the pre...

Page 6: ...t the documentation The original documentation is written in English All other languages are translations The precautions described in this document cover very important topics follow them carefully T...

Page 7: ...XPLOSION Indicates a situation that could result in explosion WARNING Indicates a situation that could result in death or serious injury WARNING FLAMMABLE MATERIAL CAUTION Indicates a situation that c...

Page 8: ...differs depending on the user permission level User or Advanced user 15 min Installer 1 h Dials and buttons You use the dials and buttons To navigate through the screens menus and settings of the LCD...

Page 9: ...e WD curve type 7 User settings Language Time date Holiday Quiet Electricity price Gas price 8 Information Energy data Malfunction history Dealer information Sensors Actuators Operation modes About Co...

Page 10: ...4P569819 1 2019 02 4 3 Possible screens Overview The most common screens are as follows a OR b c c2 c4 c1 c3 a Home screen b Main menu screen c Lower level screens c1 Setpoint screen c2 Detailed scree...

Page 11: ...e Item Description h Main zone h1 Installed room thermostat type Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface BRC1HHDA used as room thermostat Un...

Page 12: ...ature 2 Main zone Shows the applicable symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leaving...

Page 13: ...ubmenu Adjust and automatically apply the desired temperature Item Description Minimum temperature limit a1 Fixed by the unit a2 Restricted by the installer Maximum temperature limit b1 Fixed by the u...

Page 14: ...tion 1 6 bar 55 19 42 18 c 1 6 bar 55 19 42 18 d c Space heating cooling operation ON d Space heating cooling operation OFF Tank heating operation 1 6 bar 55 19 42 18 e 1 6 bar 55 19 42 18 f e Tank he...

Page 15: ...alfunction history Malfunction history 8 3 Dealer information Contact helpdesk number 8 4 Sensors Room tank or domestic hot water outside and leaving water temperature if applicable 8 5 Actuators Stat...

Page 16: ...ator will show a blue pulsation with an interval of approximately 5 seconds While the unit is in operation the status indicator will light up blue constantly To set the space operation mode 1 Go to 4...

Page 17: ...e the desired leaving water temperature INFORMATION The leaving water is the water that is sent to the heat emitters The desired leaving water temperature is set by your installer in accordance with t...

Page 18: ...including 5 4 Reheat setpoint are displayed Schedule reheat 4 7 2 Reheat mode In reheat mode the DHW tank continuously heats up to the temperature shown on the home screen example 50 C when the tempe...

Page 19: ...her dependent curve on page 24 4 7 6 Using DHW powerful operation About powerful operation Powerful operation allows the domestic hot water to be heated by the backup heater Use this mode on days when...

Page 20: ...r all three electricity prices INFORMATION Price value ranging from 0 00 990 valuta kWh with 2 significant values INFORMATION If no schedule is set the Electricity price for High is taken into account...

Page 21: ...t Schedule Program when the unit has to use which quiet mode level Off Quiet More quiet Most quiet 7 5 4 User settings Electricity price Schedule Program when a certain electricity tariff is valid Exa...

Page 22: ...last programmed action is valid up to the first action of next Monday To copy the schedule to the other weekdays 1 Select Monday Mon Sat Wed Fri Thu Tue Sun User defined 1 2 Select Copy Delete Edit C...

Page 23: ...hedule name 4 To name the current schedule browse through the character list and confirm the selected character The schedule name can contain up to 15 characters 5 Confirm the new name INFORMATION Not...

Page 24: ...onal zone Heating Additional zone Cooling Tank INFORMATION To operate weather dependent correctly configure the setpoint of the main zone additional zone or tank See 4 9 4 Using weather dependent curv...

Page 25: ...Heating Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather d...

Page 26: ...At regular outdoor temperat ures At cold outdoor temperat ures Y2 1 Y1 1 X1 1 X2 1 OK Cold Raise Raise OK Hot Lower Lower Cold OK Raise Raise Cold Cold Raise Raise Raise Raise Cold Hot Lower Raise Low...

Page 27: ...Go to 7 4 2 User settings Quiet Schedule 2 Program the schedule For more information about scheduling see 4 8 4 Schedule screen Example on page 21 4 10 3 Using holiday mode About holiday mode During...

Page 28: ...f hours For longer periods You can use the holiday mode Tips about leaving water temperature In heating mode a lower desired leaving water temperature results in lower energy consumption and better pe...

Page 29: ...onnes GWP value of the refrigerant total refrigerant charge in kg 1000 Please contact your installer for more information WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammabl...

Page 30: ...cold Possible cause Corrective action You ran out of domestic hot water because of unusual high consumption If you immediately need domestic hot water activate the DHW tank Powerful operation However...

Page 31: ...tion about the malfunction a We recommend to purge air with the air purge function of the unit to be performed by the installer If you purge air from the heat emitters or collectors mind the following...