13
|
Maintenance and service
Installer reference guide
211
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
13 Maintenance and service
NOTICE
Maintenance MUST be done by an authorized installer or service agent.
We recommend performing maintenance at least once a year. However, applicable
legislation might require shorter maintenance intervals.
NOTICE
Applicable legislation on
fluorinated greenhouse gases
requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes:
GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
13.1 Maintenance safety precautions
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
NOTICE: Risk of electrostatic discharge
Before performing any maintenance or service work, touch a metal part of the unit in
order to eliminate static electricity and to protect the PCB.
13.2 Yearly maintenance
13.2.1 Yearly maintenance: overview
▪
Brine leakage
▪
Chemical disinfection
▪
Descaling
▪
Drain hose
▪
Fluid pressure of space heating and brine circuit
▪
Pressure relief valves (1 at brine side, 1 at space heating side)
▪
Pressure relief valve of the domestic hot water tank
▪
Switch box
▪
Water and brine filters
13.2.2 Yearly maintenance: instructions
Brine leakage
Open the front panels and carefully check if brine leakage is noticeable inside the
unit. See
"6.2.2 To open the indoor unit"
55].