Binary ValueObject Instance Summary
The following table summarizes the Binary Output Objects supported:
Table 63: Binary Value Object Instance Summary
Instance
ID
Object Name
Description
Active/Inactive Text
Present Value
Access Type
BV0
RUN/STOP ACT
This object indicates the drive Run Status, regardless of the control source .
RUN/STOP
R
BV1
FWD/REV ACT
This object indicates the motor’s rotation direction, regardless of the control source .
REV/FWD
R
BV2
FAULT ACT
This object indicates the drive’s fault status .
FAULT/OK
R
BV3
EXT 1/2 ACT
This object indicates which control source is active: External 1 or External 2 .
EXT2/EXT1
R
BV4
HAND/AUTO ACT
This object indicates whether the drive is under Hand or Auto control .
HAND/AUTO
R
BV5
ALARM ACT
This object indicates the drive’s alarm status .
ALARM/OK
R
BV6
MAINT REQ
This object indicates the drive’s maintenance status . Refer to Group 29 in the drive’s
parameter descriptions .
MAINT/OK
R
BV7
DRIVE READY
This object indicates whether the drive is ready to accept a run command .
READY/NOT READY
R
BV8
AT SETPOINT
This object indicates whether the drive is at the commanded setpoint .
YES/NO
R
BV9
RUN ENA ACT
This object indicates the Run Enable command status, regardless of the control source .
ENABLE/DISABLE
R
BV10
RUN/STOP CMD
This object commands a drive start . Control requires either: Parameter 1001 value =
COMM for control by EXT1 or Parameter 1002 value = COMM for control by EXT2 .
RUN/STOP
C
BV11
FWD/REV CMD
This object commands a motor rotation direction change . Control requires 1003
= REQUEST and either: Parameter 1001 value = COMM for control by EXT1 or
Parameter 1002 value = COMM for control by EXT2 .
REV/FWD
C
BV12
RUN ENA CMD
This object commands Run Enable . Control requires parameter 1601 value = COMM .
ENABLE/DISABLE
C
BV13
EXT 1/2 CMD
This object selects ext1 or ext2 as the active control source . Control requires parameter
1102 value = COMM .
EXT2/EXT1
C
BV14
FAULT RESET
This object resets a faulted drive . The command is rising-edge triggered . Control
requires parameter 1604 value = COMM .
RESET/NO
C
BV15
MBOX READ
This object reads a parameter (defined by AV25 MBOX PARAM) and returns it in AV26
MBOX DATA .
READ/RESET
W
BV16
MBOX WRITE
This object writes the data value specified by AV26, MBOX DATA, to a parameter
(defined by AV25, MBOX PARAM).
WRITE/RESET
W
BV17
LOCK PANEL
This object locks the panel and prevents parameter changes . The corresponding drive
parameter is 1602 .
LOCK/UNLOCK
W
BV18
CTL OVERRIDE CMD
This object commands the drive into BACnet Control Override . In this mode, BACnet
takes drive control from the normal source . However, the control panel’s HAND mode
has priority over BACnet Control Override .
ON/OFF
C
BV19
CTL OVERRIDE ACT This object indicates whether the drive is in BACnet Control Override . (See BV18 .)
ON/OFF
R
BV20
START ENABLE 1
This object commands start enable1 . Control requires param 1608 value = COMM .
ENABLE/DISABLE
C
BV21
START ENABLE 2
This object commands start enable1 . Control requires param 1609 value = COMM .
ENABLE/DISABLE
C
NOTE:
For Present Value Access Types, R = Read-only,W = Writeable, C = Commandable .
Commandable values support priority arrays & relinquish defaults .