BACnet Protocol Technical Data
Binary Input Object Instance Summary
The following table summarizes the Binary Input Objects supported:
Table 61: Binary Input Object Instance Summary
Instance ID
Object Name Description
Active/Inactive Text
Present Value
Access Type
BI0
RO 1 ACT
This object indicates the status of Relay Output 1 .
ON/OFF
R
BI1
RO 2 ACT
This object indicates the status of Relay Output 2 (requires MREL-01 option) .
ON/OFF
R
BI2
RO 3 ACT
This object indicates the status of Relay Output 3 (requires MREL-01 option) .
ON/OFF
R
BI3
RO 4 ACT
This object indicates the status of Relay Output 4 (requires MREL-01 option) .
ON/OFF
R
BI6
DI 1 ACT
This object indicates the status of Digital Input 1 .
ON/OFF
R
BI7
DI 2 ACT
This object indicates the status of Digital Input 2 .
ON/OFF
R
BI8
DI 3 ACT
This object indicates the status of Digital Input 3 .
ON/OFF
R
BI9
DI 4 ACT
This object indicates the status of Digital Input 4 .
ON/OFF
R
BI10
DI 5 ACT
This object indicates the status of Digital Input 5 .
ON/OFF
R
NOTE:
For Present Value Access Types, R = Read-only,W = Writeable, C = Commandable .
Commandable values support priority arrays & relinquish defaults .
Binary Output Object Instance Summary
The following table summarizes the Binary Output Objects supported:
Table 62: Binary Output Object Instance Summary
Instance ID
Object Name Description
Active/Inactive Text
Present Value
Access Type
BO0
RO1
COMMAND
This object controls the output state of Relay 1 . This control requires that parameter 1401
value = COMM .
ON/OFF
C
BO1
RO2
COMMAND
This object controls the output state of Relay 2 . This control requires that parameter 1402
value = COMM (also requires MREL-01 option) .
ON/OFF
C
BO2
RO3
COMMAND
This object controls the output state of Relay 3 . This control requires that parameter 1403
value = COMM (also requires MREL-01 option) .
ON/OFF
C
BO3
RO4
COMMAND
This object controls the output state of Relay 4 . This control requires that parameter 1410
value = COMM (also requires MREL-01 option) .
ON/OFF
C
NOTE:
For Present Value Access Types, R = Read-only,W = Writeable, C = Commandable .
Commandable values support priority arrays & relinquish defaults .
f
Ieldbus
C
onTrols
www .DaikinApplied .com 83
OM 1190-1 • MD4 VFD