Electric Power Network Specification
Voltage (U
1
)
200/208/220/230/240 V AC 1-phase for 200 V AC drives
200/208/220/230/240 V AC 3-phase for 200 V AC drives
380/400/415/440/460/480 V AC 3-phase for 400 V AC drives
±10% variation from converter nominal voltage is allowed as default .
Short-circuit capacity
Maximum allowed prospective short-circuit current at the input power connection as defined in IEC 60439-1 is 100 kA. The drive
is suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes at the drive maximum rated
voltage .
Frequency
50/60 Hz ± 5%, maximum rate of change 17%/s
Imbalance
Max . ±3% of nominal phase to phase input voltage
Motor Connection Data
Voltage (U
2
)
0 to U
1
, 3-phase symmetrical, Umax at the field weakening point
Short-circuit protection
(IEC 61800-5-1, UL 508C)
The motor output is short-circuit proof by IEC 61800-5-1 and UL 508C .
Frequency
0…500 Hz
Frequency resolution
0 .01 Hz
Current
See section Ratings, types and voltages on page 349 .
Power limit
1 .5 · PN
Field weakening point
10…500 Hz
Switching frequency
4, 8, 12 or 16 kHz
Maximum recommended motor
cable length
R0: 30 m (100 ft), R1…R4: 50 m (165 ft)
With output chokes the motor cable length may be extended to 60 m (195 ft) for R0 and 100 m (330 ft) for R1…R4 .
To comply with the European EMC Directive, use the cable lengths specified in the table below for 4 kHz switching frequency. The
lengths are given for using the drive with the internal EMC filter or an optional external EMC filter.
4 kHz
switching frequency
Internal EMC filter
Optional external
EMC filter
Second environment
(category C3
1
)
30 m (100 ft)
30 m (100 ft) minimum
First environment
(category C2
1
)
—
30 m (100 ft)
OM 1190-1 • MD4 VFD 104 www .DaikinApplied .com
T
eCHnICal
d
aTa