Package Contents/Tools Required

Package includes:

  Thermostat on base, thermostat cover, wiring labels, screws and wall anchors, 

Installation, Operation and Application Guide

Tools required for installation:

 Drill with 3/16” bit, hammer, screwdriver

Important Safety Information

WARNING!

Always turn off power at the main power supply before installing, cleaning, or 

removing thermostat.

•  This thermostat is for 24 VAC/VDC applications only; do not use on voltages over 30 VAC/VDC
•  Do not short across terminals of system control to test operation; this will damage your thermostat 

and void your warranty

•  All wiring must conform to local and national electrical and building codes
•  Use this thermostat only as described in this manual

Specifications

Electrical rating:

  • 24 VAC/VDC (18-30 VAC/VDC)

 

• 1 amp maximum per terminal

 

• 4 amp maximum total load 

Temperature control range: 

45°F to 90°F (7°C to 32°C)   

Accuracy:

 ± 1°F (± 0.5°C)

System configurations:

 2-stage heat, 2-stage cool

Timing:

 

Backlight Operation: 13 seconds after mode change or button press

Terminations:

 -C, +R, W1, Y1, W2, Y2, G, O, S1, S2

  To Remove Existing Thermostat

ELECTRICAL SHOCK HAZARD –

 

Turn off power at the main service panel by removing 

the fuse or switching the appropriate circuit breaker to the OFF position before removing the 
existing thermostat.

1.  Turn off power to the heating and cooling system by removing the fuse or switching the appropriate 

circuit breaker off.

2.  Remove cover of old thermostat. This should expose the wires.
3.  Label the existing wires with the enclosed wire labels before removing wires.
4.  After labeling wires, remove wires from wire terminals.
5.  Remove existing thermostat base from wall.
6.  Refer to the following section for instructions on how to install this thermostat.

To Install Thermostat

ELECTRICAL SHOCK HAZARD –

 

Turn off power at the main service panel by removing 

the fuse or switching the appropriate circuit breaker to the OFF position before removing the 
existing thermostat.

 

IMPORTANT:

 

Thermostat installation must conform to local and national building and 
electrical codes and ordinances. 

 

 

Note:

 

Mount the thermostat about five feet above the floor. Do not mount the thermostat 
on an outside wall, in direct sunlight, behind a door, or in an area affected by a vent 
or duct.

1.  Turn off power to the heating and cooling system by removing the fuse or switching the appropriate 

circuit breaker off.

2.  To remove cover, insert and twist a coin or screwdriver in the slots on the sides of the thermostat.
3.  Put thermostat base against the wall where you plan to mount it (Be sure wires will feed through 

the wire opening in the base of the thermostat).

4.  Mark the placement of the mounting holes.
5.  Set thermostat base and cover away from working area.
6.  Using a 3/16” drill bit, drill holes in the places you have marked for mounting.
7.  Use a hammer to tap supplied anchors in mounting holes.
8.  Align thermostat base with mounting holes and feed the control wires through wire opening.
9.  Use supplied screws to mount thermostat base to wall.
10.  Insert stripped, labeled wires in matching wire terminals. See “Wiring Diagrams” section of this 

manual.

 

CAUTION!

Be sure exposed portion of wires does not touch other wires.

11.  Tighten screws on terminal block. Gently tug wire to be sure of proper connection. Double check 

that each wire is connected to the proper terminal. 

12.  Seal hole for wires behind thermostat with non-flammable insulation or putty.
13.  Replace cover on thermostat by snapping it in place.
14.  Turn on power to the system at the main service panel.
15.  Test thermostat operation as described in “Testing the Thermostat”.

Terminal Designator Descriptions

Parts Diagram

R12

W1 Y1 W2

O

S1

S2

668375401

Y2

Backlit Display

Reset

Configuration Switches

Mode Switch

Fan Switch

Configuration Mode

The configuration mode is used to set the Daikin Auto-changeover Electronic Thermostat to match 
your heating/cooling system. To configure the Daikin Auto-changeover Electronic Thermostat, perform 
the following steps:

1.  Remove the cover of the thermostat by gently pulling on one of the corners.
2.  Simultaneously hold the 

SW5

 and 

SW6

 buttons in for 5 seconds while the Daikin Auto-changeover 

Electronic Thermostat is in 

OFF

 mode.

3.  Press the   or   button to change settings within each screen.
4.  Press the 

SW6

 button to advance to the next screen.

 

 

Note:

 

The 

SW5

 button will return you to the previous screen.

5.  To exit configuration mode, slide the 

Mode

 switch to 

Heat

 or 

Cool

.

FILTER

DIFF

ROOM

SET

REMOTE

Configuration Mode Settings

  

The setup screens for Configuration Mode are as follows:
1. 

Heat Pump and Non Heat Pump –

 Press the   or   button to configure as 

heat pump, or non-heat pump system. Set to “O” for all Daikin WSHP, PTAC, 
PTHP and UV units.

  Press the 

SW6

 button to advance to the next screen.

FILTER

DIFF

ROOM

SET

REMOTE

2.   Set to “g”.
  Press the   or   button to set to “g”.
  Press the button to advance to the next screen.

FILTER

DIFF

ROOM

SET

REMOTE

3. 

Temperature Scale (F or C) –

 Choose Fahrenheit or Celsius.

  Press the   or   button to select.
  Press the 

SW6

 button to advance to the next screen.

  -C – 24 VAC/VDC common
 +R – 24 VAC/VDC hot
 W1 – 1st stage heat
 Y1 – 1st stage cool

Remote Sensor Installation (Optional)

Requires Daikin Remote Sensor Part Number 667720401

1.  Remove cover from remote sensor housing.
2.  Select an appropriate location for mounting the remote sensor.
3.  Mount remote sensor unit using hardware provided.
4.  Install two strand shielded wire between remote sensor and thermostat. Shielded wire must be 

used. Do not run remote sensor wire in conduit with other wires.

  • 

Wire 1

 should run between the S1 terminal on the thermostat and the S1 terminal 

on the remote sensor

  • 

Wire 2

 should run between the S2 terminal on the thermostat and the S2 terminal 

on the remote sensor

  •  Connect the shielding of the wire to the S2 terminal on the thermostat
5.  Disable the main sensor (R12) on the thermostat by cutting it from the circuit board.

FILTER

DIFF

ROOM

SET

REMOTE

FILTER

DIFF

ROOM

SET

REMOTE

5. 

2

nd

 

Stage

 

Temperature Differential 

(1°F to 6°F) (0.5°C to 3.0°C)

Set the number of degrees between when stage 1 turns on and 
when stage 2 turns on.

 

Press the   or   button to set differential value.

 

Press the 

SW6 

button to advance to the next screen.

FILTER

DIFF

ROOM

SET

REMOTE

FILTER

DIFF

ROOM

SET

REMOTE

4. 

1

st

 

Stage

 

Temperature Differential 

(1°F to 3°F) (0.5°C to 1.5°C)

Set the number of degrees between your “setpoint” temperature 
and your “turn on” temperature.

 

Press the   or   button to set differential value.

 

Press the 

SW6 

button to advance to the next screen.

 W2 – 2nd stage heat
 Y2 – 2nd stage cooling
  G – Fan
  O – Override

Wiring Diagram

24 VAC Common

Tenant Override

Fan

Cool 1

Cool 2

Heat 1

Heat 2

Alarm Output

24 VAC

C

O

G

Y1

Y2

W1

W2

A

R

Override (Optional)

Thermostat 

Terminals

TB2

MicroTech III Unit Control Board
Low Voltage Terminal Strip (Circuit 1)

Non-Programmable, Auto or Manual Changeover (P/N 668375401)

Two Stage Heat/Two Stage Cool, Night Setback and Override Feature

Note:  An additional conductor is required between “O” terminals for the override 

feature to work.

Installation, Operation & Application Guide

Version B: 10-15-13

Daikin P/N (668375401)

2 Heat/2 Cool, Auto or Manual Changeover, Hardwired

Non-Programmable Electronic Thermostat

• Configurable
• Two Stage Heat / 2 Stage Cool 

Systems

• Backlit Display
• Field Temperature Calibration
• Status Indicator Light
• Relay Outputs (minimum voltage drop 

in thermostat)

• Night Set-Back Override
• Reset